Aeration Settings; Test For Flue Spillage; Optional Brick Panel - Regency IG35-NG Owners & Installation Manual

Hide thumbs Also See for IG35-NG:
Table of Contents

Advertisement

INSTALLATION
System Data
IG35
IG35-NG: For 0 to 610 meters altitude
IG35-LPG: For 0 to 610 meters altitude
IG35-ULPG: For 0 to 610 meters altitude
Burner Inlet Orifice Sizes:
NG
LPG
Burner
#33
#51
Max. Input
NG
33.5 mj
LPG
34 mj
ULPG
28 mj
Min. Input
NG
19.6 mj
LPG
18.5 mj
ULPG
14 mj
Supply Pressure
NG
1.13 kPa
LPG
2.75 kPa
ULPG
2.75 kPa
Manifold Pressure
NG
0.87 kPa
LPG
2.61 kPa
ULPG
2.61 kPa
Electrical: 240 V. 50Hz.
Circulation: High/Off/LO speed fan,
150/89 CFM.
Log Set: Ceramic fiber, 7 per set.
Aeration Setting
NG
15mm fully open
LPG
15mm fully open
ULPG
15mm fully open

AERATION SETTINGS

The burner aeration is factory set but may need
adjusting due to either the local gas supply, air
supply or altitude. This adjustment is performed
by the installer. (Close the aeration for a more
yellow flame, or open it to make the flame
bluer).
NG:
15mm fully open
LPG:
15mm fully open
ULPG:
15mm fully open
Note: Any damage due to carboning result-
ing from improperly setting the aera-
tion controls is NOT covered under
warranty.
8
TEST FOR FLUE
SPILLAGE
A " spillage" test must be made before the
installed unit is left with the customer. Follow
the procedure below:
1) Start all exhaust fans in the home and then
ULPG
close all external doors and windows in the
#53
house.
2) Light the unit and set controls to maximum.
Turn fan off.
3) After five minutes, test that there is a "pull" on
the flue by placing a smoke match, cigarette
or similar device which gives off smoke, in
both sides of the unit. See diagram 1.
The smoke should be drawn into the unit. If the
smoke is still not drawn into the spill tube, turn
the unit off and check for the cause of the lack
of draft. If necessary, rectify.
For wind turbulent sites, a wind cap may rem-
edy the problem. These caps are not included
with the standard flue kit and will need to be
purchased separately.
Diagram 1
OPTIONAL
BRICK PANEL
1) Unwrap the brick panels from the protective
wrapping.
2) Remove the glass front and log set if already
installed.
3) Place the rear brick panel flat against the
back of the unit, by carefully slipping it be-
tween the back wall of the firebox and the
rear log tray.
4) Remove the screw on the inside top left and
right side of the firebox.
Lef t Si de
of Fi r ebox
R em ove
scr ew
5) Slide the left and right side brick panels in
place and secure using the brick retaining
clips provided and the screws removed in
step 4 as shown in the diagram below.
Scr ew
Back
br i ck
panel
Si de
br i ck
panel
Regency IG35 Gas Inbuilt Fireplace
Br i ck
R et ai ni ng
C l i p

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ig35-lpgIg35-ulpg

Table of Contents