Hydraulic Specifications; Expansion Vessel - Biasi GARDA HE SYSTEM M96.28SR/P User Manual And Installation Instructions

Wall hung, fan flue, room sealed, high efficiency gas boiler
Hide thumbs Also See for GARDA HE SYSTEM M96.28SR/P:
Table of Contents

Advertisement

Technical information
4.3

Hydraulic specifications

kPa bar
0.6
60
50
0.5
40
0.4
30
0.3
20
0.2
10
0.1
0
0.0
0
200
400
Fig. 4.3
The hydraulic specifications in Fig. 4.3 represent
the pressure (available head for the central heat-
ing system) as a function of the flow rate.
The load loss due to the boiler has already been
subtracted.
Output with thermostat cocks shut off
The boiler is fitted with an automatic by--- pass
valve (38 on page 9), which protects the primary
heat exchanger.
In case of excessive reduction or total blockage of
water circulation in the central heating system
owing to closure of the thermostatic valves or sys-
600
800
1000 1200 1400
tem component cocks, the by--- pass valve ensur-
es a minimum flow of water through the primary
heat exchanger.
4.4

Expansion vessel

Note: this boiler is designed for operation only
in a sealed central heating system
The height difference between the pressure relief
valve and the highest point in the system may be
7m at most.
For greater differences, increase the pre--- load
pressure in the expansion vessel (37 on page 9)
and the system, when cold, by 0.1 bar for each
additional 1m.
l/h
Capacity
Pre--- load pressure
Maximum volume of water
in the system *
Tab. 4.1
* Where conditions are:
--- Average maximum temperature of the system
is 80°C
--- Initial temperature when filling up the system is
10°C
For systems with volumes greater than 132 l, an
additional expansion vessel must be provided.
l
6,0
kPa
100
bar
1,0
l
132
11