Diagnostics - Remote Air Cooled

No Ice
Problem
No power to unit
No power to controller
Shut down on max.
water fill time
Shut down on
maximum freeze time
Likely Cause
Power disconnected
Transformer open
Water shut off
Water leak
Dirty condenser
Restricted location, intake air
too hot
Ice thickness sensor dirty or
disconnected
Water distributor dirty
Inlet water valve leaks through
during freeze
Connected to hot water
Incomplete harvest
High pressure cut out opened
Fan motor not turning
Water pump not pumping
Pump hose disconnected
Liquid line valve does not open
Compressor not operating
September 2006 Page 52
Probable Solution
Check breaker or fuse. Reset
or replace, restart and check
Replace transformer
Restore water supply
Check purge valve, curtain,
sump, pump hose
Clean condenser
Have condenser moved
Check ice thickness sensor
probe
Remove and clean water
distributor
Check inlet water valve
Check for bleed thru from /
missing check valve in building
water supply
Check harvest system
Check check fan motor
Check quick connects for
complete piercing
Check fan motor, check fan
blade
Check pump motor, check
controller using test mode
Check hose
Check coil of valve, check
controller using test mode.
Check compressor contactor,
check controller using test
mode