Fireplace Placement Requirements; Clearances; Raised Fireplaces - Travis Industries 564 HO GSR2 Installation Manual

Hide thumbs Also See for 564 HO GSR2:
Table of Contents

Advertisement

Fireplace Placement Requirements

The fireplace requires a 1/2" (13mm) clearance from the angled sides of the fireplace to the framing
members. No material (insulation, framing, etc.) may be placed into this area.
Fireplace must be installed on a level surface capable of supporting the fireplace and vent
Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet)
This heater may be placed in a bedroom. Please be aware of the large amount of heat this appliance
produces when determining a location.

Clearances

When installed, walls in front of the fireplace must be a minimum 12" (305mm) to the side of the
fireplace.
Due to the high temperature, the heater should be located out of traffic and away from furniture and
draperies.
Fireplace must be placed so the vents below and above the glass do not become blocked.

Raised Fireplaces

The fireplace (and hearth, if desired) may be placed on a platform designed to support the fireplace
(165 lbs., 74Kg) and vent.
The base of the fireplace must be a minimum 70" (1778mm) below the room ceiling.
© Travis Industries