Figure 2.2 Wall-Mount Unit Control Board - Bard W48A2PQ Installation And Service Instructions Manual

Free cooling unit system wall-mounted package & bard-link plc lead/lag controller
Table of Contents

Advertisement

3. If after 2 minutes, the low pressure switch is
still open, or opens again immediately aftward,
the board will delay for 2 minutes again (soft
lockout).
4. On the 3rd attempt, the board will lock out the
compressor and outdoor fan until manually reset.
High Temperature 2 Alarm – Should the shelter
controller see 90°F, both free-cooling dampers will
open (regardless of outdoor temperature) to cool
the building.
Common/Control Ground
2-10VDC Free-Cooling Damper Signal
24VAC from Transformer
24VAC Output to Motor Start Relay
24VAC Heating Stg2 Output to Limit Switch
24VAC Heating Stg1 Output to Limit Switch
FIGURE 2.2
Wall-Mount Unit Control Board
Dirty Filter Switch
High Pressure Alarm Relay
Low Pressure Switch
Air Proving Switch
Damper Blade Switch
Common
+24VAC Power Input
Smoke Alarm – Should the smoke detector send
an alarm signal to the controller, all blower,
compressor and ventilations functions cease.
Freezestat – If coil temperature below 30°F is
sensed by the freezestat, the compressor will
deactivate for 5 minutes, or until the sensor sees
55°F, whichever comes first.
24V to OA Humidity Sensor
Ground
Freezestat Sensor 10kΩ
Outdoor Air Humidity Sensor 4-20mA
Return Air Temp Sensor 10kΩ
Outdoor Air Temp Sensor 10kΩ
Mixed Air Temp Sensor 10kΩ
+ Communication Wire
+24VAC Power Input
24VAC Cooling Output to Compressor Control Module
+24VAC from Transformer
–24VAC from Transformer
– Communication Wire
Manual
2100-642
Page
39 of 82

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

W48l2pqW60a2pqW60l2pqW72a2pqW72l2pqLc5000

Table of Contents