COMPRESSOR CRANKCASE HEATER

Units are equipped with crankcase heaters that are
rated for the connnected voltage and operate during
compressor off cycle.

DIRTY FILTER SWITCH

Located inside the blower compartment, this switch
measures air pressure differential across the filter (see
Figure 2.19 on page 54). Manual reset only. Default
setting: 0.8"static, 50% blocked filter (approximately).
Temperature (F) vs. Resistance (R) of Temperature Sensor
F
R
F
196871
13.0
56985
190099
14.0
55284
183585
15.0
53640
177318
16.0
52051
171289
17.0
50514
165487
18.0
49028
159904
19.0
47590
154529
20.0
46200
149355
21.0
44855
144374
22.0
43554
139576
23.0
42295
134956
24.0
41077
130506
25.0
39898
126219
26.0
38757
122089
27.0
37652
118108
28.0
36583
114272
29.0
35548
110575
30.0
34545
107010
31.0
33574
103574
32.0
32634
100260
33.0
31723
97064
34.0
30840
93981
35.0
29986
91008
36.0
29157
88139
37.0
28355
0.0
85371
38.0
27577
1.0
82699
39.0
26823
2.0
80121
40.0
26092
3.0
77632
41.0
25383
4.0
75230
42.0
24696
5.0
72910
43.0
24030
6.0
70670
44.0
23384
7.0
68507
45.0
22758
8.0
66418
46.0
22150
9.0
64399
47.0
21561
62449
48.0
20989
60565
49.0
20435
58745
50.0
19896
TABLE 2.4
R
F
R
53.0
19374
89.0
52.0
18867
90.0
53.0
18375
91.0
54.0
17989
92.0
55.0
17434
93.0
56.0
16984
94.0
57.0
16547
95.0
58.0
16122
96.0
59.0
15710
97.0
60.0
15310
98.0
61.0
14921
99.0
62.0
14544
100.0
63.0
14177
101.0
64.0
13820
102.0
65.0
13474
103.0
66.0
13137
104.0
67.0
12810
105.0
68.0
12492
106.0
69.0
12183
107.0
70.0
11883
108.0
71.0
11591
109.0
72.0
11307
110.0
73.0
11031
111.0
74.0
10762
112.0
75.0
10501
113.0
76.0
10247
114.0
77.0
10000
115.0
78.0
9760
116.0
79.0
9526
117.0
80.0
9299
118.0
81.0
9077
119.0
82.0
8862
120.0
83.0
8653
121.0
84.0
8449
122.0
85.0
8250
123.0
86.0
8057
124.0
87.0
7869
88.0
7686
ZETTLER ISOLATION RELAYS:
WALL-MOUNT UNIT
Black Zettler surface mount relays used in the wall-
mount unit to isolate the start signal from the high
pressure relay circuit (see Figure 2.20 on page 54).
FUSES
5x20mm time delay, glass tube fuse: 250VAC rated
voltage, 35 rated amp interruption at rated voltage.
BATTERIES
Used in wall-mount unit and controller boards, flat-disk
style BR2330 3V battery. Used only for time/date during
complete power loss. Estimated lifespan 7-8 years.
F
R
7507
7334
7165
7000
6840
6683
6531
6383
6239
6098
5961
5827
5697
5570
5446
5326
5208
5094
4982
4873
4767
4663
4562
4464
4367
4274
4182
4093
4006
3921
3838
3757
3678
3601
3526
3452
Manual
Page
2100-642
53 of 82

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

W48l2pqW60a2pqW60l2pqW72a2pqW72l2pqLc5000

Table of Contents