Contents General ............... 14 Getting Other Information and Publications Topping Off System Charge ........14 Safety Practices ............14 Wall Mount General Information Important Installer Note ........... 15 Wall Mount Model Nomenclature ......4 High & Low Pressure Switch ........15 Shipping Damage .............
GETTING OTHER INFORMATION AND PUBLICATIONS FOR MORE INFORMATION, CONTACT These publications can help you install the air conditioner or heat pump. You can usually find these THESE PUBLISHERS: at your local library or purchase them directly from the publisher. Be sure to consult current edition of each ACCA Air Conditioning Contractors of America standard.
WALL MOUNT GENERAL INFORMATION AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE CONTROL MODULES REVISIONS MODEL NUMBER (See Spec. Sheet S3402) COIL OPTIONS CAPACITY VOLTS & PHASE X - Standard 48 - 4 Ton COLOR OPTIONS A - 230/208/60/1 1 - Phenolic Coated Evaporator 60 - 5 Ton X - Beige (Standard) 2 - Phenolic Coated Condenser...
5/8 inch. Any grille that meets with 5/8 inch louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used.
Figure 1 or 2. Failure to provide the 1/4 inch clearance Figure 1 is for models W48A23 and W60A23. between the supply duct and a combustible 2. On wood frame walls, the wall construction must...
FIGURE 4 ELECTRIC HEAT CLEARANCE W48A23, W48L23, W60A23, W60L23 SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURFACES. WARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting.
FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 – MOUNTING INSTRUCTIONS WALL STRUCTURE FACTORY SUPPLIED RAIN FLASHING. MOUNT ON UNIT BEFORE INSTALLATION SUPPLY AIR SUPPLY AIR SUPPLY AIR DUCT OPENING OPENING RETURN AIR RETURN AIR RETURN AIR OPENING OPENING OPENING BOTTOM MOUNTING WOOD OR STEEL SIDING BRACKET.
FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS SUPPLY DUCT MAY BE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN RAIN RAIN FLASHING RAFTERS FLASHING RAFTERS FINISHED CEILING SURFACE SUPPLY AIR DUCT SUPPLY AIR DUCT FINISHED CEILING SURFACE W/ GRILLE RETURN AIR RETURN AIR OPENING W/ GRILLE...
WIRING – LOW VOLTAGE WIRING WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information 230/208V, 1 phase and 3 phase equipment dual primary and maximum fuse or “HACR” type circuit breaker voltage transformers. All equipment leaves the factory size.
8. Store cylinders in a cool area, out of direct sunlight. TOPPING OFF SYSTEM CHARGE 9. Never heat cylinders above 125°F. If a leak has occurred in the system, Bard 10. Never trap liquid R-410A in manifold sets, gauge Manufacturing recommends reclaiming, evacuating lines or cylinders. R-410A expands significantly (see criteria above), and charging to the nameplate at warmer temperatures.
START UP (Continued) IMPORTANT INSTALLER NOTE PHASE MONITOR For improved start up performance wash the indoor coil All units with three phase scroll compressors are with a dish washing detergent. equipped with a 3 phase line monitor to prevent compressor damage due to phase reversal. HIGH &...
SEQUENCE OF OPERATION Alarm Relay Output COOLING – Circuit R-Y makes at thermostat pulling Alarm terminal is output connection for applications where alarm relay is employed. This terminal is in compressor contactor, starting the compressor and outdoor motor. (See NOTE under Condenser Fan powered whenever the compressor is locked out due to Operation if equipped with Low Ambient Control.) The HPC or LPC sequences as described.
TABLE 5 COOLING PRESSURE TABLE Air Temperature Entering Outdoor Coil °F Return Air Temp Model Pressure (DB/WB) Low Side 75/62 High Side Low Side W48A2/L2 80/67 High Side Low Side 85/72 High Side Low Side 75/62 High Side Low Side W60A2/L2 80/67 High Side...
Circuit Breaker Kit TABLE 8 ELECTRIC HEAT W60A23 Model 240V-1 208V-1 Amps BTUH Amps BTUH 20.8 17,050 18.1 12,800 41.6 34,130 36.2 25,600 W48A23 & W48L23 ARE NOT APPROVED FOR USE WITH ELECTRIC HEAT. Manual 2100-594 Page 19 of 19...