Figure 2.1 Refrigerant Sight Glass - Bard W48A2PQ Installation And Service Instructions Manual

Free cooling unit system wall-mounted package & bard-link plc lead/lag controller
Table of Contents

Advertisement

Return Air
Model
Pressure
Temperature
75° DB
Low Side
62° WB
High Side
80° DB
Low Side
W48
67° WB
High Side
85° DB
Low Side
72° WB
High Side
75° DB
Low Side
62° WB
High Side
80° DB
Low Side
W60
67° WB
High Side
85° DB
Low Side
72° WB
High Side
75° DB
Low Side
62° WB
High Side
80° DB
Low Side
W72
67° WB
High Side
85° DB
Low Side
72° WB
High Side
Low Side Pressure ±4 PSIG
High Side Pressure ±10PSIG
The refrigerant sight glass installed in this unit is not a
charging indicator. Use only universally recommended
practices of charging: superheat, subcooling,and preferably,
weighing in the correct charge. The sight glass is for
moisture reference only.
TABLE 2.1
Nominal Pressures: Models W48, W60, W72
Air Temperature Entering Outdoor Coil, Degree °F
75
80
85
129
130
132
289
309
331
138
139
141
296
317
339
143
144
146
306
328
351
121
122
124
304
325
346
129
131
133
312
333
355
134
136
138
323
345
367
116
117
119
329
350
372
124
125
127
337
359
382
128
129
131
349
372
395
FIGURE 2.1
Refrigerant Sight Glass
90
95
100
105
133
135
136
137
353
376
401
426
142
144
145
146
362
386
411
437
147
149
150
151
375
400
425
452
126
128
130
132
369
392
416
443
135
137
139
141
378
402
427
454
140
142
144
146
391
416
442
470
121
122
123
125
395
419
444
470
129
131
132
134
405
430
455
482
134
136
137
139
419
445
471
499
110
115
120
138
139
141
452
481
509
148
149
151
464
493
522
153
154
156
480
510
540
134
136
137
469
497
527
143
145
147
481
510
540
148
150
152
498
528
559
128
130
132
496
524
552
137
139
141
509
537
566
142
144
146
527
556
586
Manual
2100-642
Page
37 of 82