FX2N-32DP-IF Profibus-DP Interface Unit
1.3.4

Example Configuration

Figure 1.5: Example Configuration
A Series
Profibus-DP
network
For configuration rules, refer to section 1.3.3.
1) Check special function blocks.
a) Count special function blocks.
This 32DP-IF has 3 special function blocks connected (FX
This configuration is OK as the total number of blocks is less than 8.
b) Check the loading on the 5 V DC bus supply. Consumption values for special function
blocks can be found in Table 1.7. For maximum available current see the Table 1.6.
Table 1.8: Check 5 V DC Bus Supply
Items
FX
FX
FX
Total Consumption Values
This configuration is OK as the 5 V DC bus supply consumption value is less than 220 mA
(5 V DC bus supply capacity).
However, this system needs a supply of 455 mA from an external 24 V DC power supply, for
the special function blocks. In this case, the 32DP-IF can supply 250 mA for external 24 V
DC. See next page (check the loading on the 24 V DC service supply)
PLC
A1SJ71PB92 (software version E)
FX
-
FX
2N
32DP-IF
-ES/UL
-4AD
2N
-4DA
2N
-4DA
2N
-16EX
FX
-16EYT
2N
2N
-ESS/UL
Internal 5 V DC
30 mA
30 mA
30 mA
90 mA <220 mA
FX
-
FX
-
FX
2N
2N
2N
4AD
4DA
4DA
-4AD
1, FX
2N
External 24 V DC
55 mA
200 mA
200 mA
455 mA
Introduction 1
-
-4DA
2).
2N
1-9