Mitsubishi FX2N User Manual page 34

Profibus-dp interface unit
Hide thumbs Also See for FX2N:
Table of Contents

Advertisement

FX2N-32DP-IF Profibus-DP Interface Unit
Note 4: Error status
Data register D8029 reflects the error status of the 32DP-IF. In case of a general error (bit 0
= ON) the module tries to send a static diagnosis to the DP-master. In this case normal data
exchange is not possible. If bit 0 returns to the Off state, the static diagnosis message is
also reset.
The definition of the error bit is shown in the table below.
Table 4.9: Error status in D8029
Bit No.
Bit 0
general error
Bit 1
Reserved
External 24 V power
Bit 2
error
Bit 3 ~ 5
Reserved
Bit 6
(ref. Table
I/O bus error
4.11)
Bit 7
(ref. Table
Operation error
4.11)
Bit 8, 9
Reserved
Bit 10
(ref. Table
configuration error
4.11)
Bit 11
(ref. Table
Parameter error
4.11)
Bit 12 ~ 14 Reserved
Bit 15
RUN/STOP status
Description
No general error
Power supply is
normal
No I/O bus error
No operation error
Configuration
data valid
Parameter data
valid
RUN/STOP
switch is in RUN
position
0 (OFF)
This bit is ON if one or more error bits (bit 2, 6,
7) are ON. Check Bit 2, 6 and 7 in D8029.
DC 24 V power supply failure
I/O bus error occurred. Check extension bus
cable for I/O extension units/blocks and error
code in D8060.
Operation error occurred. Check extension bus
cable for special function blocks, and DP-mas-
ter parameter, and error code in D8067 and
D8068.
Invalid configuration data received. Check con-
figuration for 32DP-IF in the DP-master and
D8040 ~ D8055.
Invalid parameter data received. Check param-
eter for 32DP-IF in the DP-master and D200 ~
D299, and error code in D8064and D8068.
RUN/STOP switch is in STOP position
Advanced Devices 4
1 (ON)
4-8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx2n-32dp-if

Table of Contents