Error Flags - Mitsubishi FX2N User Manual

Profibus-dp interface unit
Hide thumbs Also See for FX2N:
Table of Contents

Advertisement

FX2N-32DP-IF Profibus-DP Interface Unit
8.3.2

Error Flags

Table 8.6: Error Flags
Diagnostic
Device
M8004
(ref. D8004)
M8060
(ref. D8060,
D8061)
M8061
(ref. D8060,
D8061)
M8062
(ref. D8062)
M8064
(ref. D8064
M8067
(ref. D8067)
M8068
(ref. D8068)
Name
Error occurrence
I/O configuration error
32DP-IF hardware error
PC/HPP communication error
Parameter error
Operation error
Parameter error and operation
error
Check Points
ON when one or more error flags (M8060 to
M8068) is ON. If this bit is ON, error number is
written in D8004.
If this flag is ON, check error code in D8060,
D8061 and extension cable.
If this bit is ON, check error code in D8061.
If this bit is ON, check error code in D8062.
If this flag is ON, check error code inD8064 and
DP-master setting.
If this flag is ON, check error code in D8067 and
D8068, DP-master parameter, and the extension
cable.
If M8064 or M8067 is ON, this bit would be set to
ON. This bit is cleared by resetting the power
supply.
Diagnostics 8
8-4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx2n-32dp-if

Table of Contents