Sia / Ansi Cp-01 Requirements - GE NetworX NX-4 Installation And Startup

Control/communicator
Hide thumbs Also See for NetworX NX-4:
Table of Contents

Advertisement

To meet SIA CP-01 requirements –
Minimum System Requirements: 1 control panel; 2 keypads
Remote arming shall NOT be enabled in SIA classified installations.
Off-premise transmission must be in the SIA format.
The Abort window and Entry Delay must not exceed 1 minute.
CAUTION – A call waiting cancel on a non-call waiting line will prevent successful connection to the central station.
CP-01 Feature
Description
Exit Time
Progress Annuncation / Disable
– for Silent Exit
Exit Time Restart
Auto Stay Arm on Unvacated
Premises
Exit Time and Progress
Annunciation / Disable
– for Remote Arm
Entry Delay(s)
Abort Window
– for Non-Fire Zones
Abort Window Time
– for Non-Fire Zones
Abort Annunciation
Cancel Annunciation
Duress Feature
Cross Zoning
Programmable Cross Zoning Time
Swinger Shutdown
Swinger Shutdown Disable
Fire Alarm Verification
Call Waiting Cancel
Default Changes (from prior
versions):
SIA SYSTEM REQUIREMENTS (ANSI-SIA CP-01)
Feature Description
as shown in manual
Exit 1 Delay
Exit 2 Delay
Silent Keypad Option
This feature is non-programmable in the panel.
Auto Bypass
This feature is non-programmable in the panel.
enabled.
Entry 1 Delay
Entry 2 Delay
Dialer Delay
Dialer Delay
This feature is non-programmable in the panel.
disarming.
Cancel
Duress
2 Trips on Cross Zone
Keypad sounds on Cross Zone trip
Zone Type Characteristic
Cross Zone Time
Swinger Shutdown Count
Swinger Shutdown Count
Fire Alarm Verification Time
Must be programmed as part of
the phone number
Recent Closing
Exit Error
Power Up Delay
Program
Seg / Opt
Loc
2
24
4
24
2
9 3
All annunciators enabled
1 / 3
23
-- Exit time and progress are always
1
24
3
24
8
40
8
40
-- Flashing Cancel LED goes off when
3 / 6
23
44
5 / 4
37
5
39
3 / 4
111
6
40
n/a
38
Enabled for 1 trip
n/a
38
Enabled for 1 trip
9
40
n/a
0
3 / 7
23
3 / 8
23
3
40
Factory
CP-01 Required
Default
60
45 – 240 sec.
60
45 – 240 sec.
Allowed
(individual keypads may be disabled)
Enabled
Enabled
Enabled
Enabled (may be disabled for remote arming)
30
30 – 240 sec.
30
30 – 240 sec.
30
Enabled
(may be disabled by zone/ zone
type)
30
15 – 45 sec.
Enabled
Enabled
Enabled
Disabled
Disabled
Disabled
Required
Disabled
Disabled
5 minutes
Allowed
For all non-fire zones, shut down at 1–2 trips
Allowed
Disabled
Required (depends on panel & sensors)
n/a
Required (depends on user phone line)
Enabled
Enabled
60 sec.
Setting
NOTE:
Combined
Abort
window and
Entry Delay
must not
exceed 1
minute.