Page 1
GE Zenith Controls Entelli-Switch 250 Microprocessor Controller Transfer Switch Control Panel 71R-2000 Operation and Maintenance Manual 5/03 Get other manuals https://www.bkmanuals.com...
It is designed to give highly accurate control of the transfer switch system. All GE Zenith transfer switches are designed for use on emergency or standby systems, and are rated for total system or motor loads. Transfer switches are UL Listed under Standard 1008 and CSA Certified under Standard C22.2 No. 178 and IEC Listed under Standard 947.
(Can Cause Severe Injury or Death) Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components. The safe operation of your switch is GE Zenith’s focus. Final Equipment Inspection The proper storage, installation, operation and mainte- Prior to energizing the transfer switch: nance will help increase the life of the switch.
Figure 3 CAUTIONS Certain accessories, per specific schematics, can inhibit automatic transfer. Engine Gen-Set could start when engine control wires are attached. Figure 2 (Typical) GE Zenith Controls Entelli-Switch 250 Operation and Maintenance Manual (71 -2000) Get other manuals https://www.bkmanuals.com...
This step is only performed if the NOTE Entelli-Switch 250 display Figure 4. The annunciation “DS” Option was purchased. LEDs illuminate to indicate (1) source availability, (2) ATS position, and (3) Entelli-Switch 250 control Close the external (up-stream) Source 1 function (timing). circuit breaker. NOTES...
Figure 5 shows the location of these terminals. GE Zenith Controls Entelli-Switch 250 Operation and Maintenance Manual (71 -2000) Get other manuals https://www.bkmanuals.com...
2 1 : 5 6 M O N 2 3 A P R 2 0 0 2 M O R E T E S T Entelli-Switch 250 Figure 7 GE Zenith Controls Entelli-Switch 250 Operation and Maintenance Manual (71 -2000) Get other manuals https://www.bkmanuals.com...
SET and CFG menu will show the descriptions of The Entelli-Switch 250 has many logic options. Each the options (see pages 17-18). These menus are the very controller is downloaded with options at the time of same menus that are used to access the setting and/or manufacture.
Once satisfied, the W timer will begin timing (see page 18). “Restore” must be a minimum of to transfer to Source 2. 1% below “Fail” setting. GE Zenith Controls Entelli-Switch 250 Operation and Maintenance Manual (71 -2000) Get other manuals https://www.bkmanuals.com...
Denotes an Accessory with 2 circuits as a standard. Delayed Transition Units Only. Denotes an Accessory with 3 circuits as a standard. Optional for 40-400 Amp GE Zenith Controls Entelli-Switch 250 Operation and Maintenance Manual (71 -2000) Get other manuals https://www.bkmanuals.com...
L3 Indicates Source 1 available. Can be configured by end user for 1, 7, 14, L4 Indicates Source 2 available. 28, 365 day cycle. (See page 16) GE Zenith Controls Entelli-Switch 250 Operation and Maintenance Manual (71 -2000) Get other manuals https://www.bkmanuals.com...
Page 12
Source 1 to Source2). When synchronism is accomplished, Q3 input to allow transfer to Source 2. To enable Q3 transfer will take place. option, engage Q3 jumper. GE Zenith Controls Entelli-Switch 250 Operation and Maintenance Manual (71 -2000) Get other manuals https://www.bkmanuals.com...
Page 13
Should Source 1 fail, the Generator (Source 2), will automatically start. Once transferred in Manual, the Switch maintains position selected even if selected power fails. GE Zenith Controls Entelli-Switch 250 Operation and Maintenance Manual (71 -2000) Get other manuals https://www.bkmanuals.com...
10. Press SAVE (this will enter this value and move cursor to month). 11. Use the up and down key up to change the month. GE Zenith Controls Entelli-Switch 250 Operation and Maintenance Manual (71 -2000) Get other manuals https://www.bkmanuals.com...
(ATS in S2 position)= CDT (Exerciser) 2) Press MORE timing period +T (S1 stable Timer) timing period. 3) Press START TEST TIMER (to initiate Test). GE Zenith Controls Entelli-Switch 250 Operation and Maintenance Manual (71 -2000) Get other manuals https://www.bkmanuals.com...
(24 Hour System) To save value and to To previous field move cursor to next or to exit screen. field to be changed. Figure 9 GE Zenith Controls Entelli-Switch 250 Operation and Maintenance Manual (71 -2000) Get other manuals https://www.bkmanuals.com...
Entelli-Switch 250 User Setup - CFG Menu Turn options ON or OFF via S1 OK 01 : 5 0 keypad through the CFG menu F RI 3 1 MAY 2 0 0 3 M ORE TEST Enter six digit access code...
Entelli-Switch 250 User Setup - SET Menu Change adjustable values S1 O K 01: 50 through the SET menu. FRI 31 MAY 20 03 M ORE TEST Enter six digit access code (The factory assigned six-digit access code 1 VA B = ___...
Entelli-Switch 250 User Setup - System Info View System Data S1 OK 01 : 5 0 Enter six digit access code FRI 31 MAY 2 0 03 (The factory assigned six-digit access code MO RE TE ST is located on the back of the controller) WARNING —PHASE TO PHASE VOLTAGE, S1 &...
Source 1 after the time delay of the T timer. The U engine overrun timer allows the engine generator to run unloaded for a preset cool down period. GE Zenith Controls Entelli-Switch 250 Operation and Maintenance Manual (71 -2000) Get other manuals https://www.bkmanuals.com...
"U" time delay if desired. Upon completion of the to Engine Stop "U") begins its cycle to allow Source 2 Engine (U) timing cycle, the controller sends an Engine stop signal. GE Zenith Controls Entelli-Switch 250 Operation and Maintenance Manual (71 -2000) Get other manuals https://www.bkmanuals.com...
Source 2. The SEO limit switch activates to de-ener- gize the CCEO relay. The ATS has now closed back into Source 1 position without interrupting the load. GE Zenith Controls Entelli-Switch 250 Operation and Maintenance Manual (71 -2000) Get other manuals https://www.bkmanuals.com...
10)Re-connect the transfer switch to AUTO.* * As described in the Sequence of Operation section located in the ZTSCT/ZBTSCT Series Manual (71R-5000) GE Zenith Controls Entelli-Switch 250 Operation and Maintenance Manual (71 -2000) Get other manuals https://www.bkmanuals.com...
Time to S2 S1 Stable Time to S1 Delay Source 1 Transfer to Source 2 Transfer to Source 1 Engine Source 1 Fails Cooldown Returns GE Zenith Controls Entelli-Switch 250 Operation and Maintenance Manual (71 -2000) Get other manuals https://www.bkmanuals.com...
Source 2. The SEO limit switch activates to de-ener- gize the CCEO relay. The ATS has now closed back into Source 1 position without interrupting the load. GE Zenith Controls Entelli-Switch 250 Operation and Maintenance Manual (71 -2000) Get other manuals https://www.bkmanuals.com...
Page 28
CCN - COIL CONTROL RELAY (SOURCE 1) COMMON SINGLE PHASE SOURCE 2 SENSING 3-PHASE SOURCE 1 SENSING SOURCE 1 CONTROL POWER SOURCE 2 CONTROL POWER Figure 16 GE Zenith Controls Entelli-Switch 250 Operation and Maintenance Manual (71 -2000) Get other manuals https://www.bkmanuals.com...
HAZARDOUS VOLTAGES CAN CAUSE SEVERE INJURY OR DEATH. These charts may indicate problems that require authorized GE Zenith service personnel. Hazardous voltages may exist on termination plugs other than those that go into the Entelli-Switch 250. General Troubleshooting The following troubleshooting guide is used to recognize, second suspected fault.
When performing a hi-pot or dielectric test on the power section, DISCONNECT the GE Zenith can provide complete preventative main- control panel plugs from the microprocessor tenance services. Please contact the GE Zenith Technical to avoid potential damage. Services Department for additional information. GE Zenith Controls...
Page 31
GE Zenith Controls Entelli-Switch 250 Operation and Maintenance Manual (71 -2000) Get other manuals https://www.bkmanuals.com...
Page 32
GE Zenith Controls A Product of GE Industrial Systems General Electric Company 830 West 40 Street, Chicago, IL 60609 USA 773 299-6600 , Fax: 773 247-7805 www.geindustrial.com Get other manuals https://www.bkmanuals.com...