Snorkel Termination
This appliance is approved only for 36 inch Snorkel
termination. Not approved for use with a 14 inch Snorkel.
The minimum horizontal run may be no less than 6"
(152 mm).
T he maximum horizontal run may be no more than 24
in. (610 mm.)
One 45° Elbow may be used for a corner installation as
shown in fig. 23.
Exhaust Restriction: Under normal circumstances, no
exhaust restriction is recommended. Keep the factory
setting (Position A - fully open).
f i r e - p a r t s . c o m
Insulation Requirement: Apply a minimum 1/2" thick
foil-faced ceramic insulation blanket behind the
Snorkel before attaching it to the wall (Jøtul PN 225606
is available).
Min. 12 in. (305 mm)
Max. 5 ft.. (152.4 cm)
Min. 24”
610 mm
Figure 21. Minimum vent required for horizontal termination.
Figure 22.
Maximum horizontal and vertical vent run 36" Snorkel
termination.
C L
56 1/2”
1435mm
Figure 23.
Corner installation with 36" Snorkel termination.
Maximum horizontal run is 12".
139636_02 GF 500 DV IPI January 2015
Minimum 1/2" Foil-face
Ceramic Insulation Blanket
Required
Min. 6" (152 mm)
Max. 6”
Max. 24 in. (610 mm)
(152 mm)
36”
C L
(91.5 cm)
C L
22 1/2”
(571mm)
15