Safetyconsiderations; Systemrequirements - Carrier 40MB*D Installation Instructions Manual

Ducted heat pump split system sizes 09 to 48
Hide thumbs Also See for 40MB*D:
Table of Contents

Advertisement

SAFETY
CONSIDERATIONS
Installing,
starting up, and servicing
air-conditioning
equipment
can be hazardous
due to system pressures,
electrical components,
and equipment
location
(roofs, elevated structures,
etc.).
Only trained,
qualified
installers
and service
mechanics
should
install, start-up,
and service this equipment.
Untrained
personnel
can perform
basic maintenance
functions
such
as cleaning
cots.
All other
operations
should be performed
by
trained service personnel.
When
working
on the equipment,
observe
precautions
in the
literature
and
on
tags,
stickers,
and
labels
attached
to
the
equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep
quenching
cloth and fire extinguisher
nearby when
brazing.
Use
care in handling,
rigging, and setting bulky equipment.
Read
these
insWactions
thoroughly
and follow
all warnings
or
cautions
included
in literature
and
attached to the unit. Consult
local building
codes
and National
Electrical
Code
(NEC)
for
special requirements.
Recognize
safety information.
This is the
safety-alert
symbol/_k.
Whan you see this symbol
on the unit and
in instructions
or manuals,
be alert to the potential
for personal
injury.Understand
these signal words: DANGER,
WARNING,
and
CAUTION.
These words
are used with the s_ffety-alert
symbol.
DANGER
identifies
the most serious hazards
which will result in
severe personal
injury
or death.
WARNING
signifies
hazards
which could result in personal
injury or death.
CAUTION
is used
to identify
unsafe practices
which may
result in minor personal
injury or product
and property
damage. NOTE is used to highlight
suggestions
which will result in enhanced
installation,
reliability,
or
operation.
ELECTRICAL
SHOCK
HAZARD
Failure to follow
this warning
could result in personal
injury or death.
Before installing,
modifying,
or servicing system,
main
electrical
disconnect
switch
must
be
in
the
OFF
position.
There may be more than 1 disconnect
switch.
Lock out and tag switch with a suitable warning
label.
EXPLOSION
HAZARD
Failure to follow this warning could
result in death, serious personal injury,
and/or property
damage.
Never
use
air or
gases
containing
oxygen
for leak testing
or operating
refrigerant
compressors.
Pressurized
mixtures
of air or gases
containing
oxygen can lead to an explosion.
EQUIPMENT
DAMAGE
HAZARD
Failure to follow
this caution may result in equipment
damage or improper operation.
Do not bury more than 36 in. (914 ram) of refrigerant pipe
in the ground. If any section of pipe is buried, there must be
a 6 in. (152 ram) vertical rise to the vane connections on
the outdoor units. If more than the recommended length is
buried, refrigerant may migrate to the cooler buried section
during extended periods of system shutdown. This causes
refrigerant
slugging
and
could possibly
damage the
compressor at start-up.
SYSTEM
REQUIREMENTS
Allow
sufficient
space for airflow and servicing
unit.
Recommended
Connection
Method
for Power and Communi-
......
_
"
"O
_
" t
-
ence_
Power W_mg:
The main power is supplied to the outdoor
unit. The field supplied
connecting
cable from the outdoor
unit to indoor unit consists
of
three (3) wires
and provides
the power
for the indoor
unit. Two
wires are high voltage
AC power and one is a ground wire.
Consult
your
local
building
codes
and
the
NEC
(National
Electrical
Code)
or CEC
(Canadian
Electrieal
Code)
for special
requirements.
All wires
must be sized per NEC or CEC and local codes. Use
Electrical
Data table MCA
(minimum
circuit
amps)
and MOCP
(maximum
over current protection)
to correctly
size the wires and
the disconnect
fuse or breakers respectively.
Per caution note, only copper conductors
with a minimum
300 volt
rating and 2/64-inch
thick insulation
must be used.
Communication
Wiring:
A separate shielded copper
conductor
only, with a minimum
300
volt rating and 2/64-inch
thick insulation,
must be used as the
communication
wire from the outdoor
unit to the indoor unit.
To minimize
voltage
drop of the control
wire, use the following
wire size and maximum
lengths shown in the chart below:
Wire Size
Length
ft (m)
18 AWG
50 (15)
16 AWG
50 (15) to 100 (30)
EQUIPMENT
DAMAGE
HAZARD
Failure
to fo!low
this caution
may result
in equipment
damage or improper
operation.
* Wires should be sized based on NEC and local codes.
. Use copper conductors
only with a minimum
300 volt
rating and 2/64 inch thick insulation.
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

40mb d series40mbd-01si

Table of Contents