Refrigerant Pipe - Carrier 40MB*D Installation Instructions Manual

Ducted heat pump split system sizes 09 to 48
Hide thumbs Also See for 40MB*D:
Table of Contents

Advertisement

[]
[]
[]
The service valves of the outdoor unit should
be completely
closed(as
original
status).Every
time you connect,first
loosen
the nuts, then connect the flare pipes within 5 minutes. If the
nuts have been
loosened
for a long time,
dusts and other
impurities
may
enter
the pipe
system
and may
cause
a
malfunction.So
please
expel
the air out of the pipe
with
refrigerant before connection.
Expel the air(refer to the "8.1")after
connecting
the refrigerant
pipe with the indoor unit and the outdoor unit.
Then fasten the nuts at the service valves.
Bend the connecting pipe of small wall thickness.
Cut out a proper
concave
at the bending
part of the
insulating pipe.
Then expose the pipe(cover it with tape after bending).
To prevent
twisting,
please
bend the pipe at a proper
radius.
NOTE
The bending angle should not exceed 90. o
The bending position is preferably in the middle of the bendable
pipe.
Do not bend the pipe more than three times.
Be sure to use the same insulating materials when you buy the
brass pipe. (More than 0.35in/9mm thick)
3
Connect the pipes.
4
Expel the air with a vacuum pump or refrigerant.
5
Open the service valves of the outdoor unit.
6
Check the refrigerant
leakage.
Check all the joints
with the leak detector or soap water.
7
Cover the joints
of the connecting
pipe with the
insulation foam, and bind them well with the tape to
prevent potential leakage.
=
8.1
REFRIGERANT PIPE(theunitwiththe
twinsfunction)
Length and drop height permitted
of the
refrigerant
piping
Note:
Reduced
length
of the branching
tube is the 1.64ft
/0,5mof the equivalent
length of the pipe,
Table.8-1
2.
Place
The Pipe
[]
Drill a hole in the wall (suitable just for the size of the wall
sleeve), then set the fittings such as the wall sleeve and its
cover.
[]
Bind the connecting
pipe and the cables together tightly with
binding tapes.
[]
Pass the bound connecting
pipe through the wall sleeve from
outside.
Make sure the pipe allocation
does not damage
the
copper tubes.
98.42ft/30m
L+LI+L2
164.04ft/50m
49.21ft/15m
L1,L2
32.8ft/10m
L1-L2
65.8fti20m
HI
1.64fti0.5m
H2
t
t
Outdoor unit
'
¢---
/
The line branch pipe
L2
L1
Indoor unit
o
c_
0
oC
cq
0
-o
0
_=-_
Fig.8-1
]6