Refrigerant Pipe Connection - Carrier 40MB*D Installation Instructions Manual

Ducted heat pump split system sizes 09 to 48
Hide thumbs Also See for 40MB*D:
Table of Contents

Advertisement

Note: All used branch
pipe must be produced by Midea,
otherwise the unit will
malfunction.
The indoor units should
be installed equivalently
at both sides of the U type branch
pipe.
8.2 Size of joint pipes
Table.8-2
Size of joint pipes for 410A
¢0.375in/9.5
¢0.25in/6.35
CE-FQZHN-01C
¢0.5in/12.7
¢0.25in/6.35
CE-FQZHN-01C
¢0.626in!15.9
¢0.375in!9.5
CE-FQZHN-01C
8.3
1
2)
Vacuum
with vacuum
pump
3)
Use the vacuum pump with the vacuum level lower than
-14.5PSi!-0.1MPa
and the air
discharge
capacity
above
1.4CFM!40L/min.
It is not necessary to vacuum the outdoor unit. Don't open the
outdoor unit gas and liquid pipe shut-off valves.
Make sure the vacuum pump registers as -14.5PSi/-0.1MPa
or
below after 2 hours or longer operation. If the pump operated 3
hours or above can not achieve -14.5PSi!-0.1MPa
or below,
please check whether there is a water mix or gas leak inside of
the pipe.
Connect with vacuum pump
.0.
I Perform the pump (last for 2 hrs or above)
,,_
I1. Close-off the valve of I
vacuum meter
When get the vacuum level
I
-0.1MPa
the pump should
2. Cut off the connection I
run for 2()-60 mins
J
between pressure meter
I
/
and vacuum pump.
,_
/
3. Close the vacuum
I
[ vacuum pump
.G
Place the vacuum state unused (1 hrs or above)l
I
I
,_
CAUTION
Fig.8-2
Don't mix up the different
refrigerants
or abuse the tools and
measurements
which directly contact with refrigerants.
Don't adopt refrigerant gas for air vacuuming.
If vacuum level could not get to -14.5PSi/-0.1MPa,
please check
whether resulted by leakage and confirm the leakage site.If no
leakage, please operate the vacuum pump again 1 or 2 hrs.
8.4
Refrigerant
amount
to be added
Calculate the added refrigerant according
to the diameter
and
the length
of the liquid
side pipe of the outdoor/indoor
unit
connection. The refrigerant is R410A.
Table.8-3
¢0.25in/6.35
0.0331b/0.015kg
¢0.375in/9.52
0.0661b/0.030kg
1) The branching pipe must be installed horizontally, error angle
of it should not large than 10 °. Otherwise,
a malfunction will
occur.
U-shaped branching pipe
I
A
!
A direction view
Wrong
Correct
Horizontal surface
Fig.8-3
9.
REFRIGERANT PIPE CONNECTION
9.1
Expel The Air
1
Flaring
Cut a pipe with a pipe cutter. (Refer to Fig.9-1)
2
X X
/__
9_
_Lean eludj_
bull_
I
I
I
Fig.9-1
Insert a flare nut into a pipe and flare the pipe.
Fasten
the nut
Put the connecting pipes at the proper position,
wrench
the nuts with hands then fasten
it with
two wrenches simultaneously.
(Refer to Fig.9-2)
__
Fig.9-2
CAUTION
Too much torque will harm the bellmouthing
and too little will
cause leakage.
Please determine
the torque according
to
Table 9-1.
17