Note: All used branch
pipe must be produced by Midea,
otherwise the unit will
malfunction.
The indoor units should
be installed equivalently
at both sides of the U type branch
pipe.
8.2 Size of joint pipes
Table.8-2
Size of joint pipes for 410A
¢0.375in/9.5
¢0.25in/6.35
CE-FQZHN-01C
¢0.5in/12.7
¢0.25in/6.35
CE-FQZHN-01C
¢0.626in!15.9
¢0.375in!9.5
CE-FQZHN-01C
8.3
1
2)
Vacuum
with vacuum
pump
3)
Use the vacuum pump with the vacuum level lower than
-14.5PSi!-0.1MPa
and the air
discharge
capacity
above
1.4CFM!40L/min.
It is not necessary to vacuum the outdoor unit. Don't open the
outdoor unit gas and liquid pipe shut-off valves.
Make sure the vacuum pump registers as -14.5PSi/-0.1MPa
or
below after 2 hours or longer operation. If the pump operated 3
hours or above can not achieve -14.5PSi!-0.1MPa
or below,
please check whether there is a water mix or gas leak inside of
the pipe.
Connect with vacuum pump
.0.
I Perform the pump (last for 2 hrs or above)
,,_
I1. Close-off the valve of I
vacuum meter
When get the vacuum level
•
I
-0.1MPa
the pump should
2. Cut off the connection I
run for 2()-60 mins
J
between pressure meter
I
/
and vacuum pump.
,_
/
3. Close the vacuum
I
[ vacuum pump
.G
Place the vacuum state unused (1 hrs or above)l
I
I
,_
CAUTION
Fig.8-2
Don't mix up the different
refrigerants
or abuse the tools and
measurements
which directly contact with refrigerants.
Don't adopt refrigerant gas for air vacuuming.
If vacuum level could not get to -14.5PSi/-0.1MPa,
please check
whether resulted by leakage and confirm the leakage site.If no
leakage, please operate the vacuum pump again 1 or 2 hrs.
8.4
Refrigerant
amount
to be added
Calculate the added refrigerant according
to the diameter
and
the length
of the liquid
side pipe of the outdoor/indoor
unit
connection. The refrigerant is R410A.
Table.8-3
¢0.25in/6.35
0.0331b/0.015kg
¢0.375in/9.52
0.0661b/0.030kg
1) The branching pipe must be installed horizontally, error angle
of it should not large than 10 °. Otherwise,
a malfunction will
occur.
U-shaped branching pipe
I
A
!
A direction view
Wrong
Correct
Horizontal surface
Fig.8-3
9.
REFRIGERANT PIPE CONNECTION
9.1
Expel The Air
1
Flaring
•
Cut a pipe with a pipe cutter. (Refer to Fig.9-1)
2
O×
X X
/__
9_
_Lean eludj_
bull_
I
I
I
Fig.9-1
•
Insert a flare nut into a pipe and flare the pipe.
Fasten
the nut
•
Put the connecting pipes at the proper position,
wrench
the nuts with hands then fasten
it with
two wrenches simultaneously.
(Refer to Fig.9-2)
__
Fig.9-2
CAUTION
Too much torque will harm the bellmouthing
and too little will
cause leakage.
Please determine
the torque according
to
Table 9-1.