Product Information Linear Smoke Detector Fireray 50/100RV
6.2. Arrangement of the detectors in a tilted roof
Depending on the roof pitch α and the room height R
the detector and the reflectors must be arranged such that the
light beam in distance D
6.3. Arrangement of the detectors in a saddleback roof
Depending on the roof pitch α
and the room height R
and the reflectors must be arranged
such that light beam in distance D
runs below the ceiling.
runs below the ceiling.
L
, the detector
H
L
Depending on local rules and regulations, different distances may be
prescribed or permissible if necessary.
H
D
L
α
min. 0.5 m
max. 7m
max. 14 m
D
α
min. 0.5 m
max. 7m
max. 14 m
Seite 9 von 22
,
D
L
max. 14 m
D
L
L
min. 0.5 m
max. 14 m
max. 7 m
601-F.01U.002.705
ST-FIR/ PRM1/ zab
PI - 34.85
D
L
min. 0.5 m
max. 7 m
D
L
A1.en / 29.12.2004