Bosch Fireray 50 Product Information page 14

Linear smoke detector
Hide thumbs Also See for Fireray 50:
Table of Contents

Advertisement

Product Information Linear Smoke Detector Fireray 50/100RV
Connection of two Fireray 50/100RV to fire panel with cross zoning via an NBK
100 LSN and two NSB100 LSNs
1
Bridges Br1, Br2 on the NSB 100 in position 2-3 (see connection of one Fireray 50/100RV)
Contacts in open position
2
Configuration for LSN:
Parameterize the NSB in the control panel to control output
KA1-KA2/KR-R-RR and "Control with Fireray".
Observe assignment to detector groups/detectors (see example).
Fireray 50/100 RV
DIP switch
(recommended settings)
Operating mode
switch
Output
for key switch
(optional)
rd
bl
ye
Fireray 50/100 RV
DIP switch
(recommended settings)
Operating mode
switch
Output
for key switch
(optional)
rd
bl
ye
2
bl
gn
wh
6 DA mini
distributor
2
bl
gn
wh
6 DA mini
distributor
NSB 100
(if voltage drop
Seite 14 von 22
- U
+U
- U
I3
I4
<
6 V)
EV 24 V - 24 V
PI - 34.85
NBK 100 LSN
Parameterize, e.g. to 127/1
150/1 cross zoning with
VI1
VI1
Line 1
Line 1
500, current trigger
VI2
VI2
criterion
V1
V1
500/1 cross zoning
Line 2
Line 2
with 150, current
V2
V2
trigger criterion
NSB 100 LSN
Parameterize, e.g. to 127/2
V1 KR
V2 KA1
Parameterize, e.g. to
V3 KA2
KA1-KA2-KR-150/2
1
NSB 100 LSN
Parameterize, e.g. to 127/3
V1 KR
V2 KA1
Parameterize, e.g. to
KA1-KA2-KR-500/2
V3 KA2
1
+U
601-F.01U.002.705
A1.en / 29.12.2004
ST-FIR/ PRM1/ zab