Installation Instructions
DS240 and DS241
Long Range Beam Smoke Detectors
1.0
Description
The DS240 and DS241 are long range projected beam type smoke
detectors which consist of a separate transmitter and receiver. Internal
pointability provides coverage flexibility without the need for brackets.
Automatic Signal Synchronization and Range Adjustment reduce
installation costs. Selectable sensitivity and alarm response time
provide installation flexibility.
2.0
Specifications
• Operating Voltage: DS240: 18.0 VDC to 32.0 VDC
DS241: 10.2 VDC to 15.0 VDC
• Standby Current:
DS240: Receiver: 45 mA @ 24.0 VDC
DS241: Receiver: 50 mA @ 12.0 VDC
• Receiver Alarm
Current:
DS240: 60 mA @ 24.0 VDC
DS241: 75 mA @ 12.0 VDC
• Range (distance
between transmitter
and receiver):
30 ft to 350 ft (9 m to 107 m)
• Spacing (distance
between systems): Allow no more than 60 ft (18 m) between
systems. Sixty foot spacing is confirmed
by Underwriters Laboratories, Inc. testing.
• Pointability:
Internally pointable optics for ±90°
horizontal, and ±10° vertical adjustment.
• Sensitivity:
Field selectable for 20, 30, 40, 50, 60, or
70 percent beam obscuration.
• Alarm Contacts:
Normally Open contacts rated 1 A,
60 VDC maximum for DC resistive loads.
Do not use with capacitive or inductive
loads.
• Trouble Contacts:
Normally Closed contacts rated 1 A, 60 VDC
maximum for DC resistive loads. Do not
use with capacitive or inductive loads.
• Aux. Alarm
Contacts:
Form "C" (NO, C, NC) contacts rated 1 A,
60 VDC maximum for DC resistive loads.
Do not use with capacitive or inductive
loads.
• Tamper:
Receiver:
Transmitter: Upon cover's removal, cover
• System Signaling:
Conventional 4-wire system. Not for use
with systems that incorporate an alarm
verification feature.
• Signal Delay:
Fire:
Trouble:
• Temperature:
The storage and operating temperature
range is -22°F to +130°F (-30°C to +54°C).
For UL Listed installations, the range is
+32°F to +130°F (0°C to +54°C).
• Mounting:
The units are designed to be mounted to
4 in. (10 cm) square or octagonal
electrical boxes (not supplied).
Downloaded from: http://www.guardianalarms.net
Transmitter: 20 mA @ 24.0 VDC
Transmitter: 20 mA @ 12.0 VDC
Access door tamper switch in
series with trouble contacts.
tamper switch interrupts
transmission.
Selectable 30 sec or 5 sec
20 ± 2 sec
• Listings and
Approvals:
UL
ULC
MSFM
NY City MEA
CSFM
FM
• Standard
Accessories:
DIS2000 Remote Test/Indicator Plate and
Test Cable
• Options:
DIS240 Remote Indicator Plate, TK240
Field Test Kit, AL240 Alignment Light, and
TC2000 Test Cord.
3.0
Principle of Operation
Each DS240 or DS241 beam smoke detector has a separate
transmitter and receiver. The transmitter transmits an invisible infrared
beam of a specific frequency and intensity. The receiver detects, then
measures the beam's intensity (see Figure 1 ).
Figure 1 - Infrared Transmission
As the beam is obscured by smoke, the receiver senses a decrease
in the signal strength and measures that decrease. The receiver
compares the signal level with two preset thresholds: an alarm
threshold which is set using the sensitivity switch and a trouble
threshold which is preset at approximately 10%. If the signal falls
below the alarm threshold for the programmed alarm period, the
receiver signals an alarm (see Figure 2 ).
Figure 2 - Beam Obscuration
If the signal falls below the trouble threshold for more than 20 sec,
such as might happen if the beam is blocked by a foreign object, the
receiver signals a trouble condition (see Figure 3 ).
Figure 3 - Beam Blockage
The receiver automatically compensates for the gradual loss of signal
due to dust/dirt build-up on the cover. After 50 percent of the signal is
lost, the receiver will indicate a trouble. When the dust/dirt build-up is
cleaned or the blockage is removed, the detector automatically goes
back to its normal operation level.
A trouble will be indicated at the receiver if the beam strength is
increased by more than 20% for greater than 20 sec. Causes include
improper initial alignment or the removal of a partial beam blockage
at the time of alignment. Preform a fine-tune alignment (see Section
7.3 Fine Tune Alignment on page 6).
S3019
CS692
Permit #1943
Acceptance #MEA274-93-E
#7260-1062:106
Job #OX2A9.AY

Advertisement

loading

Summary of Contents for Bosch DS240

  • Page 1 DS240 and DS241 Long Range Beam Smoke Detectors Description The DS240 and DS241 are long range projected beam type smoke detectors which consist of a separate transmitter and receiver. Internal pointability provides coverage flexibility without the need for brackets. Automatic Signal Synchronization and Range Adjustment reduce installation costs.
  • Page 2: Installation Considerations

    Use the following chart to determine the proper wire size, wire length and the number of transmitter and receiver pairs that can be used. © 2004 Bosch DS240/DS241 Installation Instructions 14.5 ft. (4.4 m) s r i...
  • Page 3: Access Door

    Mounting surfaces should be supported at opposite corners to reduce the pendulum effect. • Always select surfaces not subject to building movement. The automatic compensation circuits of the DS240 and DS241 will eliminate most problems created by normal building expansions and contractions. In some unusual circumstances, the walls and...
  • Page 4 Terminal 9. Remote Indicator Plate The DIS2000 Remote Indicator Plate is shipped with the DS240/ DS241 as a standard accessory. Although the Remote Indicator Plate is not required, the manufacturer recommends its installation to provide a means of checking the condition of the detector from ground level.
  • Page 5 Horizontal Fine Tuning adjustment screw to fine tune the image to the center of the mirror (in-line with the front and rear bore sights). DS240/DS241 Installation Instructions • Replace and secure the transmitter's cover when this alignment procedure is complete.
  • Page 6 The reference voltage of the detectors should be checked at least once a year (or more often if required by local regulations or authorities having jurisdiction). Clean covers are necessary for proper reference voltage readings. © 2004 Bosch DS240/DS241 Installation Instructions LEDs Setup Button...
  • Page 7 As shown in Figure 17 , if the expected smoke density is 0.5 percent per ft (per 30 cm), the obscuration at 50 ft (15 m) is 20 percent and at 250 ft (95 m) it is 73 percent. DS240/DS241 Installation Instructions 30% 40% UL Maximum Sensitivity...
  • Page 8 The booklet, "How to Identify and Resolve Radio-TV Interference Problems,” prepared by the Federal Communications Commission (FCC) may prove helpful. This booklet is available from the U. S. Government Printing Office, Washington, DC 20402. Please specify Stock No.004-000-00345-4. Page 8 P/N: 22066P © 2004 Bosch DS240/DS241 Installation Instructions...
  • Page 9: Troubleshooting

    Troubleshooting DS240/DS241 Installation Instructions © 2004 Bosch P/N: 22066P Page 9...
  • Page 10 10.0 Installing Multiple Units Page 10 P/N: 22066P © 2004 Bosch DS240/DS241 Installation Instructions...
  • Page 11: Quick Start Installation Flow Chart

    11.0 Quick Start Installation Flow Chart DS240/DS241 Installation Instructions © 2004 Bosch P/N: 22066P Page 11...
  • Page 12 © 2004 Bosch 130 Perinton Parkway, Fairport, NY 14450-9199 USA Customer Service: (800) 289-0096; Technical Support (888) 886-6189 22066P Installation Instructions DS240/DS241 Long Range Beam Smoke Detectors 7/04 Page 12 of 12...