Product Information Linear Smoke Detector Fireray 50/100RV 1. Product Description The Fireray 50/100RV is a linear optical black and white smoke detector. The detector is a retro- operation device, i.e. the transmitter and the receiver are located in one housing with the control unit. A prism reflector is mounted opposite the detector and reflects the infrared beam to the transmitter/receiver combination.
PI - 34.85 Product Information Linear Smoke Detector Fireray 50/100RV 3. Features D Compact housing with integrated transmitter, receiver, and control unit D Detector ranges: - Fireray 50RV 5 m to 50 m - Fireray 100RV 50 m to 100 m D Side detection breadth of 7.5 m on both sides of the beam center line (according...
PI - 34.85 Product Information Linear Smoke Detector Fireray 50/100RV 4. Device Design 4.1. Detectors 120 mm Detector baseplate Operating mode switch Receiver window Gimbal bearing Transmitter window Knurled screw for horizontal adjustment (on right of detector) Operating indica- tor LEDs...
PI - 34.85 Product Information Linear Smoke Detector Fireray 50/100RV 5. Functional Description The transmitter emits an infrared light beam (880 nm) that is focused through a lens and invisible. The light beam is reflected by 180_ by the prism reflector mounted opposite and returned to the transmitter/receiver combination.
PI - 34.85 Product Information Linear Smoke Detector Fireray 50/100RV 6. Planning Notes It is very important that the system be carefully planned and precisely adjusted, to ensure that the detector responds as early as possible. The response time of the system is dependent on the installation location, the volume of smoke generated, the ceiling construction and air ventilation.
PI - 34.85 Product Information Linear Smoke Detector Fireray 50/100RV D Heat accumulation under roof surfaces can hinder the travel of climbing smoke to the ceiling. The detector must therefore be mounted below an expected heat accumulation. This can mean that the benchmark values for D specified in the table must be exceeded.
PI - 34.85 Product Information Linear Smoke Detector Fireray 50/100RV 6.2. Arrangement of the detectors in a tilted roof Depending on the roof pitch α and the room height R the detector and the reflectors must be arranged such that the light beam in distance D runs below the ceiling.
PI - 34.85 Product Information Linear Smoke Detector Fireray 50/100RV 7. Mounting Tips D Observe the planning notes in Section 6. D Usually, the detector and the reflector are installed at the same height and oriented towards each other. The relatively broad angle of the IR beam eases adjustment and guarantees reliable long - term stability.
Page 11
PI - 34.85 Product Information Linear Smoke Detector Fireray 50/100RV DIP switches D The DIP switches can be accessed through the round recess in the detector base plate. Table 2.: Functions of the DIP switch settings DIP switch settings Function...
PI - 34.85 Product Information Linear Smoke Detector Fireray 50/100RV 7.2. Mounting the Fireray 50/100RV D To make mounting easier, you can remove the detector cover by gently raising the upper and lower edges. D The mounting slots (see Fig. 3.), which are positioned at a 90_angle, enable vertical or horizontal mounting of the detector.
PI - 34.85 Product Information Linear Smoke Detector Fireray 50/100RV 7.4. Connection Connection of a Fireray 50/100RV using a NSB100 LSN at the fire panel NSB 100 LSN Bridges Br1, Br2 in position 2-3 Contacts in open position I1 NLT1 Configuration for LSN: I2 ⊥...
Page 14
Connection of two Fireray 50/100RV to fire panel with cross zoning via an NBK 100 LSN and two NSB100 LSNs Bridges Br1, Br2 on the NSB 100 in position 2-3 (see connection of one Fireray 50/100RV) Contacts in open position...
PI - 34.85 Product Information Linear Smoke Detector Fireray 50/100RV 8. Start- Up 8.1. Setting up the detector D Start the «Prism Targeting»mode by moving the operating mode switch (see Fig. 3.) up (if the detector is mounted vertically) or to the right (if the detector is mounted horizontally).
Page 16
PI - 34.85 Product Information Linear Smoke Detector Fireray 50/100RV D Follow the flow chart to perform the calibration process: Switch center Alignment Mode Yellow LED lights up for approx. 5 s No signal: back to Steady Wait until both LEDs have...
PI - 34.85 Product Information Linear Smoke Detector Fireray 50/100RV D When the calibration procedure is complete, move the operating mode switch (see Fig. 3.) to the bottom (if the detector is mounted vertically) or to the left (if the detector is mounted horizontally).
DIN VDE 0833 apply, which refer to the maintenance interval according to the manufacturer’s instructions. D Bosch ST recommends a functional and visual inspection at least once a year. D Maintenance and inspection work should be carried out regularly and by trained personnel.
PI - 34.85 Product Information Linear Smoke Detector Fireray 50/100RV 10. Technical Data Operating voltage 10 V DC . . . 30 V DC Current consumption: - in standby mode in standby mode < 4 mA @ 24 V < 4 mA @ 24 V - in alarm/malfunction <...
PI - 34.85 Product Information Linear Smoke Detector Fireray 50/100RV Appendices 11.1. Installation protocol Installation company: Type of object: Installation location: Installation date: Total number of all linear detectors: j Fireray 50RV Detector version: j Fireray 100RV Detector – reflector distance:...
PI - 34.85 Product Information Linear Smoke Detector Fireray 50/100RV 11.2. Fault diagnosis Fault indicator Possible cause Action Beam path blocked by an obstacle Check and/or ensure free visual line in the area between the detector and the reflector. Reflector is contaminated/covered/ Check the status of the reflector and has fallen down.