6-3. FAN OPERATION

TIME SUN MON TUE WED THU FRI SAT
TIMER
Hr
AFTER
AFTER
ERROR CODE
û Fû C
û Fû C
ONLY1Hr.
TEMP.
MENU
ON/OFF
BACK
MONITOR/SET
DAY
OPERATION
PAR-21MAA
CLOCK
Control modes
Set by remote controller.
1. Fan
When [Auto] is set, fan speed becomes [Low].
2-1. Drain pump control
2. Drain pump
The drain pump turns ON for the specified amount of time when any of the following
conditions is met:
ON for 3 minutes after the operation mode is switched from COOL or DRY to
another operation mode (FAN).
ON for 6 minutes after the float switch is submerged in the water when the
float swich control judges the sensor is in the water.
2-2. Float switch control
• Float switch control judges whether the sensor is in the air or in the water by
turning the float switch ON/OFF.
In the water : Detected that the float switch is ON for 15 seconds.
In the air
3. Vane
Same as the control performed during the COOL operation, but with no restriction
(up/down vane change)
on the vane's downward blow setting
<How to operate>
Press POWER ON/OFF button.
Press the operation MODE button to display FAN.
ON
OFF
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
ON/OFF
FILTER
CHECK
TEST
CLEAR
Type
4 speeds + Auto type
[Low], [Med2], [Med1], [High], [Auto]
: Detected that the float switch is OFF for 15 seconds.
Control details
Fan speed notch
16
Remarks
· Same control
as COOL
operation