Vitodens 222-F, type B2SA
Variable speed heating circuit pump in the Vitodens 222-F
The integral circulation pump is a highly efficient pump with substan-
tially lower power consumption than conventional pumps.
The pump speed and consequently the pump rate are regulated sub-
ject to the outside temperature and the switching times for heating or
reduced mode. The control unit transmits the current default settings
to the circulation pump via an internal data BUS.
The min. and max. speed and the speed in reduced mode can be
adjusted at the control unit on the existing heating system by using
codes.
In the delivered condition, the minimum pump rate (coding address
"E7") and the maximum pump rate (coding address "E6") are set to
2
the following values:
Rated heating output range in
kW
3.2-13
3.2-19
5.2-26
Residual head of the integral circulation pump
Vitodens 222-F, 3.2-19 kW
500
50
450
L
400
40
K
350
H
300
30
G
250
E
200
20
D
150
C
B
100
10
A
50
0
0
0
100
Flow rate in l/h
M Upper operational limit
VIESMANN
16
(cont.)
Speed settings in the delivered
condition in %
Min. pump rate
Max. pump
rate
20
20
30
F
200
300
400
500
Specification – circulation pump
Rated heating output
Circulation pump
Rated voltage
Power consumption
– Max.
– Min.
– Delivered condition
55
65
65
600
700
800
900
kW
3.2-13
3.2-19
Type
UPM2
UPM2
15-50
15-50
V~
230
230
W
37
37
W
6
6
W
20
25
M
1000
1100
1200
VITODENS
5.2-26
UPM2
15-70
230
70
6
35