Before Installation; Precautions For R-410A; Installation; Handling - Daikin RXYSQ4M7V3B Installation Manual

Hide thumbs Also See for RXYSQ4M7V3B:
Table of Contents

Advertisement

3.
B
EFORE INSTALLATION
Since design pressure is 3.8 MPa or 38 bar, pipes of larger
wall thickness may be required. Refer to paragraph
"7.1. Selection of piping material" on page

3.1. Precautions for R-410A

The refrigerant requires strict cautions for keeping the system
clean, dry and tight.
-
Clean and dry
Foreign materials (including mineral oils or moisture) should be
prevented from getting mixed into the system.
-
Tight
Read
"8. Precautions on refrigerant piping" on page 6
and follow these procedures correctly.
Since R-410A is a mixed refrigerant, the required additional
refrigerant must be charged in its liquid state. (If the refrigerant
is in state of gas, its composition changes and the system will
not work properly).
The connected indoor units must be indoor units designed
exclusively for R-410A.

3.2. Installation

For installation of the indoor unit(s), refer to the indoor unit
installation manual.
Never operate the air conditioner with the discharge pipe
thermister (R3T), suction pipe thermister (R2T) and pressure
sensors (S1NPH, S1NPL) removed. Such operation may burn
out the compressor.
Be sure to confirm the model name and the serial no. of the
outer (front) plates when attaching/detaching the plates to avoid
mistakes.
When closing the service panels, take care that the tightening
torque does not exceed 4.1 N•m.

3.3. Handling

As shown in the figure, bring the unit slowly by grabbing the left and
right grips.
Place your hands on the corner instead of holding the suction inlet in
the side of the casing, otherwise the casing could be deformed.
Take care not to let hands or objects come in contact with
rear fins.
RXYSQ4~6M7V3B
VRVII-S system air conditioner
4PW17806-1C
4.
This is a class A product. In a domestic environment this product may
cause radio interference in which case the user may be required to
take adequate measures.
5.
1
Select an installation site where the following conditions are
satisfied and that meets with your customer's approval.
-
carefully
-
-
-
-
-
-
-
2
When installing the unit in a place exposed to strong wind, pay
special attention to the following.
Strong winds of 5 m/sec or more blowing against the outdoor
unit's air outlet causes short circuit (suction of discharge air),
and this may have the following consequences:
-
-
-
-
Refer to the figures for installation of this unit in a place where
the wind direction can be foreseen.
Turn the air outlet side toward the building's wall, fence or
screen.
Set the outlet side at a right angle to the direction of the wind.
Strong wind
3
Prepare a water drainage channel around the foundation, to
drain waste water from around the unit.
S
ELECTING INSTALLATION SITE
Make sure to provide for adequate measures in order
to prevent that the outdoor unit be used as a shelter
by small animals.
Small animals making contact with electrical parts can
cause malfunctions, smoke or fire. Please instruct the
customer to keep the area around the unit clean.
Places which are well-ventilated.
Places where the unit does not bother next-door neighbours.
Safe places which can withstand the unit's weight and
vibration and where the unit can be installed level.
Places where there is no possibility of flammable gas or
product leak.
Places where servicing space can be well ensured.
Places where the indoor and outdoor units' piping and wiring
lengths come within the allowable ranges.
Places where water leaking from the unit cannot cause
damage to the location (e.g. in case of a blocked drain pipe).
Places where the rain can be avoided as much as possible.
Deterioration of the operational capacity.
Frequent frost acceleration in heating operation.
Disruption of operation due to rise of high pressure.
When a strong wind blows continuously on the face of the
unit, the fan can start rotating very fast until it breaks.
Make sure there is enough room to do the installation
Blown air
Strong wind