Precautions On Installation; Installation Method For Prevention Of Falling Over; Method For Removing Transport Fittings; Installation Servicing Space - Daikin RXYSQ4M7V3B Installation Manual

Hide thumbs Also See for RXYSQ4M7V3B:
Table of Contents

Advertisement

4
If the water drainage of the unit is not easy, please build up the
unit on a foundation of concrete blocks, etc. (the height of the
foundation should be maximum 150 mm).
5
If you install the unit on a frame, please install a waterproof plate
within 150 mm of the underside of the unit in order to prevent the
invasion of water from the lower direction.
6
When installing the unit in a place frequently exposed to snow,
pay special attention to the following:
-
Elevate the foundation as high as possible.
-
Remove the rear suction grille to prevent snow from
accumulating on the rear fins.
7
If you install the unit on a building frame,
please install a waterproof plate (within
150 mm of the underside of the unit) or
use a drain plug kit (option) in order to
avoid the drainwater dripping.
The equipment described in this manual may cause
electronic noise generated from radio-frequency energy.
The equipment complies to specifications that are
designed to provide reasonable protection against such
interference. However, there is no guarantee that
interference will not occur in a particular installation.
It is therefore recommended to install the equipment and
electric wires keeping proper distances away from stereo
equipment, personal computers, etc...
1
Personal computer or radio
2
Fuse
3
Earth leak detector
4
Remote controller
5
Cool/heat selector
6
Indoor unit
In extreme circumstances you should keep distances of
3 m or more and use conduit tubes for power and
transmission lines.
5.
P
RECAUTIONS ON INSTALLATION
Check the strength and level of the installation ground so that
the unit will not cause any operating vibration or noise after
installation.
In accordance with the foundation drawing in the figure, fix the
unit securely by means of the foundation bolts. (Prepare four
sets of M12 foundation bolts, nuts and washers each which are
available on the market.)
It is best to screw in the foundation bolts until their length are
20 mm from the foundation surface.
A
140
620
B
45
421
612
A Discharge side
B Bottom view (mm)
C Drain hole
Installation manual
4
(See figure 2)
140
C

5.1. Installation method for prevention of falling over

If it is necessary to prevent the unit from falling over, install as shown
in the figure.
prepare all 4 wires as indicated in the drawing
unscrew the top plate at the 4 locations indicated A and B
put the screws through the nooses and screw them back tight
C
A
location of the 2 fixation holes on the front side of the unit
B
location of the 2 fixation holes on the rear side of the unit
C
wires: field supply
5.2. Method for removing transport fittings
The transportation fittings (2 yellow pieces) are provided on the leg of
the compressor for protecting the unit during transport. Remove them
as shown in
figure 3
and described below.
A
Compressor
B
Fixing nut
C
Transport fitting
1
Slightly loosen each fixing nut (B).
2
Remove each transport fitting (C) as shown in
3
Tighten each fixing nut (B) again.
CAUTION
If the unit is operated with the transport fittings attached,
abnormal vibration or noise may be generated.
6.
I
NSTALLATION SERVICING SPACE
The connection piping outlet direction in the installation shown in
figure 4
is frontward or downward. The unit of numeric values is
mm.
When routing the piping backward, secure space of ≥250 mm on
the right side of the unit.
(A) In case of non-stacked installation
Suction side obstacle
Discharge side obstacle
Left side obstacle
Right side obstacle
Top side obstacle
Obstacle is present
B
A
A
figure
3.
(See figure 4)
1
In these cases, close the
bottom of the installation
frame to prevent the
discharged air from
being bypassed
2
In these cases, only 2
units can be installed.
3
In these cases, no
restriction of height L1.
This situation is not
allowed
RXYSQ4~6M7V3B
VRVII-S system air conditioner
4PW17806-1C