Preparations Before Installation And Installation - Daikin FTQ24PAVJU Installation Manual

Hide thumbs Also See for FTQ24PAVJU:
Table of Contents

Advertisement

Where piping between indoor and outdoor units is
possible within the allowable limit. (Refer to the installa-
tion manual for the outdoor unit.)
If the a return-air duct is not installed, carefully select
the place and method of product installation so that air
fl ow into the product will not be blocked.
If installed vertically
(Top view)
(Front view)
Fig. 1-1
If installed horizontally
(Front view)
Air inlet
(Side view)
24 or
more
Fig. 1-2
English
24 or more
(length : in.)
Air outlet
H
Air inlet
Air outlet
H
H
WARNING
When installing the unit horizontally, be sure to tilt the unit in
the direction shown in Fig. 1-2. If the unit is tilted in any other
way, water can leak.
Ensure suffi cient space for the bottom of the product
(H dimensions) so that a downward slope of 1/100 can
be maintained for drain piping, as described for the intake
duct installation and in "6. DRAIN PIPING WORK".
[ PRECAUTION ]
Install the indoor and outdoor units, power supply wiring
and connecting wires at least 3.5 ft. away from televi-
sions or radios in order to prevent image interference or
noise. (Depending on the radio waves, a distance of
3.3 ft. may not be suffi cient to eliminate the noise.)
If installing the wireless kit in a room with electronic
fl uorescent lighting (inverter or rapid start type), the
remote controller's transmission distance may be short-
ened. Indoor units should be installed as far away from
fl uorescent lighting as possible.
DANGER
Do not install unit in an area where fl ammable materials are
present due to the risk of an explosion resulting in serious
injury or death.
WARNING
If the supporting structural members are not strong enough
to take the unit's weight, the unit could fall out of place and
cause serious injury.
4.
PREPARATIONS BEFORE INSTALLA-
TION AND INSTALLATION
(1)
When installing the product, refer to "3. SELECTING
INSTALLATION SITE" and consider the product size
as shown Fig. 2 and Table 1.
D
1
C
Gas line
3-1/4
Liquid line
1-3/16
H
(1-3/16)
Fig. 2
B
E
11
2-7/8
I
(1-3/16)
(length: in.)
4

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ftq18pavju