Basket Right Short To Ground; Basket Up Override Open Circuit; Basket Up Override Short To Battery; Basket Up Override Short To Ground - JLG 1250AJP Troubleshooting Manual

Hide thumbs Also See for 1250AJP:
Table of Contents

Advertisement

1.35 BASKET RIGHT SHORT TO GROUND

Flash Code: 3-4
Basket right short to ground. The platform module J7 platform rotate right output [X169.6] is shorted to ground. See 1.378
COMMON STG PROCEDURE on Pg. 175.

1.36 BASKET UP OVERRIDE OPEN CIRCUIT

Flash Code: 3-3
Basket up override open circuit. The ground module J2 platform level up override output [X002.5] is open. If the open is in or
near the platform up solenoid [X136], the fault 1.39 BASKET UP SHORT TO BATTERY OR OPEN CIRCUIT on Pg. 45 should
also be active. See 1.377 COMMON STB OR OC PROCEDURE on Pg. 174.

1.37 BASKET UP OVERRIDE SHORT TO BATTERY

Flash Code: 3-3
Basket up override short to battery. The ground module J2 platform level up override output [X002.5] is shorted to battery. If
there are no open wires, the fault 1.39 BASKET UP SHORT TO BATTERY OR OPEN CIRCUIT on Pg. 45 should also be
active. See 1.377 COMMON STB OR OC PROCEDURE on Pg. 174.

1.38 BASKET UP OVERRIDE SHORT TO GROUND

Flash Code: 3-3
Basket up override short to ground. The ground module J2 platform level up override output [X002.5] is shorted to ground.
If there are no open wires, the fault 1.40 BASKET UP SHORT TO GROUND on Pg. 45 should also be active. See 1.378
COMMON STG PROCEDURE on Pg. 175.

1.39 BASKET UP SHORT TO BATTERY OR OPEN CIRCUIT

Flash Code: 3-4
Basket up short to battery or open circuit. The platform module J7 platform level up output [X169.15] is shorted to battery or
open. If there are no open wires, the fault 1.37 BASKET UP OVERRIDE SHORT TO BATTERY on Pg. 45 should also be
active. See 1.377 COMMON STB OR OC PROCEDURE on Pg. 174.

1.40 BASKET UP SHORT TO GROUND

Flash Code: 3-4
Basket up short to ground. The platform module J7 platform level up output [X169.15] is shorted to ground. If there are no
open wires, the fault 1.38 BASKET UP OVERRIDE SHORT TO GROUND on Pg. 45 should also be active. See 1.378 COM-
MON STG PROCEDURE on Pg. 175.

1.41 BATTERY LOW

Flash Code: 4-4
Battery low. A warning that the voltage at ground module J8 [X008.2] is below 11 volts. Remove any corrosion on battery ter-
minals and battery cable terminals. Recharge or replace battery.

1.42 BATTERY TOO HIGH - SYSTEM SHUT DOWN

Flash Code: 4-4
Battery too high - system shut down. The voltage at ground module J8 [X008.2] is above 18.69 volts. The system will shut
down. Check battery and battery connections or replace battery.

1.43 BATTERY TOO LOW - SYSTEM SHUT DOWN

Flash Code: 4-4
Battery too low - system shut down. A warning that the voltage at ground module J8 [X008.2] is below 9 volts. The system
will shut down after about 5 seconds. Remove any corrosion on battery terminals and battery cable terminals. Recharge or
replace battery.
3128411
SECTION 1 - FAULT DICTIONARY AND SELECTED TROUBLESHOOTING
1250AJP
1-45