SPECTRACOOL™

Air Conditioner

n43 Model
INSTRUCTION MANUAL
© 2013 Pentair Equipment Protection
89074138
Rev. J
P/N 89068451

Advertisement

Table of Contents
loading

Summary of Contents for Pentair SPECTRACOOL 43

  • Page 1: Air Conditioner

    SPECTRACOOL™ Air Conditioner n43 Model INSTRUCTION MANUAL © 2013 Pentair Equipment Protection 89074138 Rev. J P/N 89068451...
  • Page 2: Table Of Contents

    Basic Air Conditioning Trouble Shooting Check List - Remote Access Control Version ........................36 Symptoms and Possible Causes - Remote Access Control Version ..............................37 WARRANTY ............................................38 RETURN AND REPAIR POLICY .....................................38 LIMITATION OF LIABILITY ......................................39 © 2013 Pentair Equipment Protection 89074138 - 2 -...
  • Page 3: Receiving The Air Conditioner

    Damage evident upon receipt should be noted on the freight bill. Damage should be brought to the attention of the delivering carrier -- NOT to Pentair Equipment Protection -- within 15 days of delivery. Save the carton and packing material and request an inspection. Then file a claim with the delivering carrier.
  • Page 4: Technical Information

    The contactor on the 1 phase 115V model uses a 115 V coil. The 3 phase model uses a 230 V coil. The contactor on the 1-phase 230V model uses a 230V coil (controller option only). © 2013 Pentair Equipment Protection 89074138...
  • Page 5: Phase Monitor (N431246Gxxx Only)

    This transformer powers the temperature display only. 115/230 V TO 24 V TRANSFORMER AND RELAY (OPTIONAL) This transformer and relay are used to start/stop the unit by using a customer supplied, remote mounted door switch. © 2013 Pentair Equipment Protection 89074138 - 5 -...
  • Page 6: Schematics And Wiring Diagrams For Thermostat Control

    SCHEMATICS AND WIRING DIAGRAMS FOR THERMOSTAT CONTROL N43 115V 1-PHASE GENERIC SCHEMATIC (ACTUAL UNIT OPTIONS MAY VARY) 05-2001-193 N43 230V 1-PHASE GENERIC SCHEMATIC (ACTUAL UNIT OPTIONS MAY VARY) 05-2001-192 © 2013 Pentair Equipment Protection 89074138 - 6 -...
  • Page 7: N43 460V 3-Phase Generic Schematic (Actual Unit Options May Vary)

    N43 460V 3-PHASE GENERIC SCHEMATIC (ACTUAL UNIT OPTIONS MAY VARY) 89069911 © 2013 Pentair Equipment Protection 89074138 - 7 -...
  • Page 8: N43 115V 1-Phase Generic Wire Diagram (Actual Unit Options May Vary)

    CAP. START RELAY ENCLOSURE WHT25 IMPELLER RED R WHT61 CAP. YEL4 ENC. AMB. AMBIENT IMPELLER YEL S RED R AMBIENT IMPELLER BLK20 BLK12 COMPRESSOR COMP HTR OR C/E 89069906 (OPTIONAL) (OPTIONAL) © 2013 Pentair Equipment Protection 89074138 - 8 -...
  • Page 9: N43 230V 1-Phase Generic Wire Diagram (Actual Unit Options May Vary)

    RED5 CAP. START RELAY ENCLOSURE IMPELLER RED R WHT61 CAP. YEL4 ENC. AMB. AMBIENT IMPELLER YEL S RED R AMBIENT IMPELLER BLK12 BLK20 COMPRESSOR COMP HTR 89073638 OR C/E (OPTIONAL) (OPTIONAL) © 2013 Pentair Equipment Protection 89074138 - 9 -...
  • Page 10: N43 400/460V 3-Phase Generic Wire Diagram (Actual Unit Options May Vary)

    N43 400/460V 3-PHASE GENERIC WIRE DIAGRAM (ACTUAL UNIT OPTIONS MAY VARY) © 2013 Pentair Equipment Protection 89074138 - 10 -...
  • Page 11: Dimensional Drawing

    DIMENSIONAL DRAWING WITH THERMOSTATS 89068457 © 2013 Pentair Equipment Protection 89074138 - 11 -...
  • Page 12: Installation Instructions

    24 VAC terminal strip by noting the locations on the correct wiring diagram. 7. Set thermostat for required cabinet temperature. Refer to Sequence of Operation on page 9 for thermostat adjustment and operation. SURFACE MOUNT Figure 1 Cutout Dimensions © 2013 Pentair Equipment Protection 89074138 - 12 -...
  • Page 13: Remote Access Control (Optional)

    Start-up Request AMBER Not Used Not Used AMBER Not Used Not Used AMBER Heater Active Not Used Alarm Active Not Used AMBER Controller Active Not Used AMBER Not Used Not Used © 2013 Pentair Equipment Protection 89074138 - 13 -...
  • Page 14: Displaying And Changing Program Variables

    The Remote Access Control has a normally open dry contact alarm output with a resistive load rating of 250 VAC at 3 amps. Two yellow 18 AWG wires located at the back of the air conditioner provide a connection to this output. © 2013 Pentair Equipment Protection 89074138...
  • Page 15: Alarm Input Connection

    Read and change Gateway IP Address, Device IP Address, Subnet Mask, Trap IP Address and Community • Read and change Unit Identification • Read and change the state of IP addressing (static or dynamic) • Read current Alarm Status © 2013 Pentair Equipment Protection 89074138 - 15 -...
  • Page 16: Software And Mib File Downloads

    To change to statically assigning IP Address Mode • Uncheck Use DHCP Server checkbox • Enter Device IP Address, Subnet Mask, Gateway IP Address, Trap IP Address and Community • Click Load Ethernet Info button © 2013 Pentair Equipment Protection 89074138 - 16 -...
  • Page 17: Ethernet Communication Mode

    Click Load Ethernet Info button • ALARM LOG ACCESSIBLE WITH SNMP • Using custom software with Hoffman cooling provided MIB file gives the ability to view a log of the last 25 alarms © 2013 Pentair Equipment Protection 89074138 - 17 -...
  • Page 18: Remote Access Control Pin-Out

    Y (na) U2 INPUTS GND (na) T1, EVAP IN THERMISTOR T2, EVAP OUT THERMISTOR T1, T2 GND CONTROLLER POWER BLK40 CONTROLLER POWER WHT41 POWER GROUND BLACK U3 DATA DIRECTION GREEN DATA WHITE © 2013 Pentair Equipment Protection 89074138 - 18 -...
  • Page 19: Schematic And Wiring Diagram For Remote Access Control

    SCHEMATIC AND WIRING DIAGRAM FOR REMOTE ACCESS CONTROL N43 1-PHASE GENERIC SCHEMATIC (ACTUAL UNIT OPTIONS MAY VARY) © 2013 Pentair Equipment Protection 89074138 - 19 -...
  • Page 20: N43 460V 3-Phase Generic Schematic For Remote Access Control (Actual Unit Options May Vary)

    N43 460V 3-PHASE GENERIC SCHEMATIC FOR REMOTE ACCESS CONTROL (ACTUAL UNIT OPTIONS MAY VARY) © 2013 Pentair Equipment Protection 89074138 - 20 -...
  • Page 21: N43 1-Phase Generic Wire Diagram For Remote Access Control (Actual Unit Options May Vary)

    N43 1-PHASE GENERIC WIRE DIAGRAM FOR REMOTE ACCESS CONTROL (ACTUAL UNIT OPTIONS MAY VARY) © 2013 Pentair Equipment Protection 89074138 - 21 -...
  • Page 22: N43 460V 3-Phase Generic Wire Diagram For Remote Access Control (Actual Unit Options May Vary)

    N43 460V 3-PHASE GENERIC WIRE DIAGRAM FOR REMOTE ACCESS CONTROL (ACTUAL UNIT OPTIONS MAY VARY) © 2013 Pentair Equipment Protection 89074138 - 22 -...
  • Page 23: Dimensional Drawings

    DIMENSIONAL DRAWINGS N43 GENERIC MODEL DRAWING WITH REMOTE ACCESS CONTROL 89082929 © 2013 Pentair Equipment Protection 89074138 - 23 -...
  • Page 24: Installation Instructions With Remote Access Control

    Electrical circuit should be fused with slow blow or HACR circuit breaker. 6. Set controller setpoints for required cabinet temperature. Refer to DISPLAYING AND CHANGING PROGRAM VARIABLES on page 14 for setpoint adjustment and operation. Surface Mount Figure 2 Cut-out Drawing © 2013 Pentair Equipment Protection 89074138 - 24 -...
  • Page 25: Maintenance

    1. Flush the filter with warm water from the exhaust side to the intake side. DO NOT USE CAUSTICS. 2. After flushing, allow filter to drain. Placing it with a corner down will assure complete drainage. © 2013 Pentair Equipment Protection 89074138...
  • Page 26: Condenser And Evaporator Air Movers

    CAUTION Operation of the air conditioner in areas containing airborne caustics or chemicals can rapidly deteriorate filters, condenser coils, blowers and motors, etc. Contact Pentair Equipment Protection for special recommendations. REFRIGERANT LOSS Each air conditioner is thoroughly tested prior to leaving the factory to insure against refrigeration leaks. Shipping damage or microscopic leaks not found with sensitive electronic refrigerant leak detection equipment during manufacture may require repair or recharging of the system.
  • Page 27: Refrigerant Properties Chart (R 134A)

    Amps(A) In(°F) Delta(°F) Delta(°F) 65-80 8.5-10.9 17-23 27-36 N431216GXXX 80-100 9.9-13.4 17-28 30-43 65-80 4.4-6.4 20-32 22-26 N431226GXXX 80-100 5.4-7.6 26-36 20-30 65-80 2.4-3.2 17-29 29-40 N431246GXXX 80-100 2.6-3.4 23-33 32-40 © 2013 Pentair Equipment Protection 89074138 - 27 -...
  • Page 28: Unit Characteristics

    +/- 10% of rated Cooling Amps at Max Conditions 16.6/22.0 8.7/9.1 3.4/3.8 Heating Amps 12.2 Compressor RLA / LRA 9.6/57.0 4.9/38.0 2.1/16.0 Evaporator Fan RLA .78/.93 .39/.53 .39/.53 Condenser Fan RLA .78/.93 .39/.53 .39/.53 © 2013 Pentair Equipment Protection 89074138 - 28 -...
  • Page 29: Service Data

    10-1061-16 10-1061-16 10-1061-16 Transformer, Input Power 10-1006-128 Controller, Basic 89075653 Thermistor 89075654 Bridge Rectifier 89087424 Controller Wires with pins (24) 89083091 Communication Board 89082033 Communication Cable 89080313 315 mA Fuse 89085115 © 2013 Pentair Equipment Protection 89074138 - 29 -...
  • Page 30: N43-1216-Gxxx Pressure Tables

    N43-1216-GXXX PRESSURE TABLES N431216GXXX 50hz L=SUCTION (± 5PSIG); H=HEAD (-10/+20PSIG) ENCLOSURE TEMPERATURE (°F) °F N431216GXXX 60hz L=SUCTION (± 5PSIG); H=HEAD (-10/+20PSIG) ENCLOSURE TEMPERATURE (°F) °F © 2013 Pentair Equipment Protection 89074138 - 30 -...
  • Page 31: N43-1226-Gxxx Pressure Tables

    N43-1226-GXXX PRESSURE TABLES N431226GXXX 50hz L=SUCTION (± 5PSIG); H=HEAD (-10/+20PSIG) ENCLOSURE TEMPERATURE (°F) °F N431226GXXX 60hz L=SUCTION (± 5PSIG); H=HEAD (-10/+20PSIG) ENCLOSURE TEMPERATURE (°F) °F © 2013 Pentair Equipment Protection 89074138 - 31 -...
  • Page 32: N43-1246-Gxxx Pressure Tables

    N43-1246-GXXX PRESSURE TABLES N431246GXXX 50hz L=SUCTION (± 5PSIG); H=HEAD (-10/+20PSIG) ENCLOSURE TEMPERATURE (°F) °F N431246GXXX 60hz L=SUCTION (± 5PSIG); H=HEAD (-10/+20PSIG) ENCLOSURE TEMPERATURE (°F) © 2013 Pentair Equipment Protection 89074138 - 32 -...
  • Page 33 NOTES © 2013 Pentair Equipment Protection 89074138 - 33 -...
  • Page 34: Trouble Shooting

    (replace upper access panel for safety). This will activate the switch in the thermostat. Turn the power on and if all impellers and the compressor come on, the thermostat needs to be replaced. © 2013 Pentair Equipment Protection 89074138 - 34 -...
  • Page 35: Symptoms And Possible Causes - Thermostat Version

    Short in system Drain plugged Drain tube kinked Getting water in enclosure Enclosure not sealed (allowing humidity in) Mounting gasket damaged For additional technical support, contact Pentair Equipment Protection at 800-896-2665. © 2013 Pentair Equipment Protection 89074138 - 35 -...
  • Page 36: Basic Air Conditioning Trouble Shooting Check List - Remote Access Control Version

    6. The compressor and the condenser (Ambient or “HOT” air) impeller(s) should turn on. Is there adequate airflow? YES, proceed to step 7. NO, possible problem: » Open motor winding(s) » Stuck impeller(s) Repair or Replace » Obstructed wheel(s) defective part » Defective motor capacitor(s) © 2013 Pentair Equipment Protection 89074138 - 36 -...
  • Page 37: Symptoms And Possible Causes - Remote Access Control Version

    Short in system Drain plugged Drain tube kinked Getting water in enclosure Enclosure not sealed (allowing humidity in) Mounting gasket damaged For additional technical support, contact Pentair Equipment Protection at 800-896-2665. © 2013 Pentair Equipment Protection 89074138 - 37 -...
  • Page 38: Warranty

    Pentair Equipment Protection approval. Pentair Equipment Protection must be notified of a claim in writing not later than fourteen (14) days from the date when Buyer has become aware of such occurrence, or where the defect is such that it may cause damage, immediately, such notice containing a description of how the defect manifests itself.
  • Page 39: Limitation Of Liability

    B. All returns to Pentair Equipment Protection must be securely packed, using original cartons if possible. All returns must have the RMA number visible on the outside of the carton. Pentair Equipment Protection is not responsible for material damaged in transit. Any refrigerant-bearing Goods must be shipped upright for return.
  • Page 40 Pentair Equipment Protection 2100 Ho man Way Minneapolis, MN 55303 USA +1.763.422.2211 +1.763.576.3200 PentairEquipmentProtection.com © 2013 Pentair Equipment Protection 89074138 Rev. J P/N 89068451...