Deadband; Smooth Set Recovery(Ssr); Ssr Stage 2 Lock Out; Temperature Offset - Lennox ComfortSense 7500 Installation And Setup Manual

Color touchscreen programmable thermostat
Hide thumbs Also See for ComfortSense 7500:
Table of Contents

Advertisement

DEADBAND

Default is 2°F. The deadband setting is the
minimum difference between the cooling and
heating set points. This setting is used in cool/heat
mode to ensure smooth equipment operation. The
deadband is adjustable from 2 to 9°F. Use the + or -
option to select desired deadband. Press < to
return to previous menu.

SMOOTH SET RECOVERY(SSR)

Options are enable or disable. Default is enable.
When enabled, smooth set back begins recovery
up to two hours before the programmed time so
that the programmed temperature is reached at
the corresponding programmed event time.
Assume 12°F per hour for first stage gas/electric
heating and 6°F per hour for first stage
compressor based heating or cooling. With
Smooth Set Back disabled, the control will start a
recovery at the programmed time.
NOTE - Smooth Set Back and Stage2 Lock Out
operations vary depending on equipment (see
table 1).

SSR STAGE 2 LOCK OUT

Default is 20 minutes. Use the + or - option to set
the number of minutes before the programmed
event time that stage 2 is allowed to operate (20 to
120 minutes in 10 minute increments). Press < to
return to previous menu.
DEALER INFORMATION
This allows the installer to add dealer name,
address, phone, email, website and number.
Press < to return to previous menu.

TEMPERATURE OFFSET

Default is 0°F. This setting can be used to offset
the displayed space temperature by up to +/- 5°F.
This offset also applies to the control temperature.
Press < to return to previous menu.
HUMIDITY OFFSET
Default is 0%. This can be used to offset the
displayed and controlled space relative humidity
(RH) by up to +/- 10% RH. Press < to return to
previous menu.