Gas furnace – var. speed blower – var. speed inducer – two stage heat – direct vent (45 pages)
Summary of Contents for Trane THV1M087A936
Page 1
18-DE01D1-8 AVAILABLE IN FRENCH CANADIAN (FC) Installer’s Guide OIL FIRED CENTRAL FURNACE THV1M087A936, 948, 9V3, 9V5SA - Highboy TLF1M087A936, 948, 9V3, 9V5SA- Lowboy Front Flue TLR1M087A936, 948, 9V3, 9V5SA - Lowboy Rear Flue TDF1M087A936, 948, 9V3, 9V5SA - Downflow/ Horizontal ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES IMPORTANT —...
Installer’s Guide Contents 8. The furnace may be used for temporary heating of buildings or structures under construction only when the following conditions have been met: CONTENTS a. The furnace venting system must be complete and installed per manufacturers instructions. INSTALLATION GUIDELINES b.
Installer’s Guide The minimum clearances from furnace casing CLOSET AND ALCOVE INSTALLATION surfaces to combustible materials are: All furnace models may be installed in a closet or alcove - 3 inches from casing sides and rear on combustible flooring with specified (standard) clear- - 8 inches from front casing of furnace to the closet ances to combustible construction.
Installer’s Guide 1) When the furnace is installed in the horizon- AIR FOR COMBUSTION AND VENTILATION tal configuration, the oil burner must be ▲ CAUTION mounted in an upright position. It will be necessary VENTILATION REQUIRED! to remove the burner then cutoff one (1) of the Relief openings in the front or top of the furnace cas- threaded burner-mounting studs before attempting ing should not be obstructed or blocked.
Page 12
Installer’s Guide Often, household chemicals contain chloride-bearing b. In buildings of unusually tight construction (e.g. compounds. There are many compounds representative those having continuous water vapor barriers; of this classification of chemicals. A few common ex- tightly-fitting, or weather-stripped, doors and amples are listed below.
Installer’s Guide If an exhaust fan, additional air consuming machines The inside area of the chimney liner should (e.g. an air compressor), or a return air grill is present equal, at minimum, the area of the vent pipe exiting in the furnace room, there should be increased concern the furnace- EXAMPLE: π...
Installer’s Guide If the roof is flat rather than the normal residential Pitched roof, refer to Figure 6 for proper clearances. FLUE/ CHIMNEY/ VENT CONNECTOR ▲ CAUTION PROPER VENTING REQUIRED! DO NOT install a manual damper in the chimney or vent connector.
Page 15
Installer’s Guide All chimney clean-out doors and flue connections must fit tightly so they will seal to avoid air leaks. If chimney flues are divided or there are multiple flues within one chimney, make sure there are no openings in the partition separating the divided or individual flues.
Installer’s Guide To prevent condensation, it is necessary that the PREVENTION OF CHIMNEY CONDENSING: internal chimney wall temperature always be kept ▲ WARNING above the dew point. If the chimney is a masonry PROPER VENTING REQUIRED! type, it may have to be fitted with a flue liner, when Improper venting may lead to condensation in the the temperature loss is too great for the furnace.
Installer’s Guide Two (2) problems typically arise when power venting If the furnace is used in connection with summer air any oil fired appliance: conditioning (cooling), the furnace should be installed in 1) Soot buildup may occur at an accelerated rate on parallel with, or on the upstream side of, the evaporator critical components of the furnace oil burner, e.g.
Installer’s Guide The side casings have each been pre-punched with four The oil burner was installed in the furnace at the fac- (4), square, knockout openings for use in locating the tory. In the field, if it is necessary to adjust the heating proper position for the return air filter rack.
Installer’s Guide - Adjusting the fuel pump pressure Manual venting of the fuel unit is required on initial - Setting the draft control start-up. If connecting a two-pipe fuel supply, install the fuel unit bypass plug. NOTICE: This oil furnace must be installed and ad- The oil supply inlet pressure to the fuel unit cannot justed by qualified oil heating dealers using calibrated exceed 3 psi.
Installer’s Guide A disconnect switch equipped with overcurrent protec- tion (e.g. a time delay-type fuse or inverse time, circuit breaker) should be installed in the service line for shut- ting down and protecting the furnace and electrical sys- tem. Since the furnace is entirely pre-wired at the factory, it is only necessary to connect the building electrical ser- SEE TABLE 1 vice lines to the two (2) pigtail wires extending from the...
Page 21
Installer’s Guide Using 18 gauge control wire, connect control wiring to thermostat as shown in the following illustrations. If the thermostat does not have an isolated heating circuit (RH), then install a pilot duty rated, 24 volt, relay (RLY00975, field supplied). This relay is shown as R1 in the illustrations.
Page 22
Installer’s Guide VARIABLE SPEED OIL FURNACE CONNECTION LOCATIONS AND LOW VOLTAGE HOOK UP DIAGRAMS (SINGLE STAGE COOLING) WITH 24V RELAY VARIABLE SPEED V3, V5 LOW VOLTAGE WIRING VARIABLE SPEED OIL FURNACE SINGLE STAGE COOLING CONNECTIONS LOCATIONS THERMOSTAT SINGLE STAGE ONE STAGE VS Route electrical power circuit through outside OIL FURNACE AIR CONDITIONER...
Page 23
Installer’s Guide LOW VOLTAGE HOOK UP DIAGRAMS FOR VARIABLE SPEED OIL FURNACE (TWO STAGE/ STEP COOLING) VARIABLE SPEED OIL FURNACE TWO STAGE COOLING VARIABLE SPEED OIL FURNACE TWO STEP COOLING WITH 24V RELAY WITH 24V RELAY ONE STAGE VS TWO STEP ONE STAGE VS TWO STAGE THERMOSTAT...
Page 24
BAYSUB10ABASEAA DIMENSIONS Down f low Furnace Combustible Sur f ace-Mounting Base Trane 6200 Troup Highway 02/09 Tyler, TX 75707 Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right For more information contact to change design and specifications without notice.