Pipe Length And The Elevation - Carrier xpower blue II 42KCL109313G Service Manual

C10 inverter series
Table of Contents

Advertisement

6.3 Pipe length and the elevation

The pipe length and refrigerant amount:
Capacity
Btu/h
38KCD109313G+ 38KCD109313G
42KCD112313G+ 38KCD112313G
42KCD118313G + 38KCD118313G
42KCD124313G+ 38KCD124313G
Caution:
The capacity test is based on the standard length and the maximum permissive length is based on the
system reliability.
The oil trap should be installed per 5-7 meters.
Pipe size
Standard
length
Gas
Liquid
(m)
3/8''
1/4''
(Ф9.52)
(Ф6.35)
1/2"
1/4''
(Ф12.7)
(Ф6.35)
5/8''
3/8''
(Ф15.9)
(Ф9.52)
15
Max.
Max.
Elevation
Length
B (m)
A (m)
5
8
5
8
5
10
Additional
refrigerant
(g/m)
20
20
20
20
25
40