6.3 Pipe length and the elevation

Pipe size
Capacity
Btu/h
Gas
5/8'' (Ф16.0)
21K/24K/28K
Caution:
Oil Traps: oil traps must be fitted to vertical suction risers where outdoor unit is above indoor unit. Fit a trap at the bottom
of the vertical rise and then at 5m (maximum) intervals.
If the outdoor unit is installed below the indoor unit (fig 1) – no trap is required in such installation.
If the units are installed at the same level – no trap is required in such installation.
Standard
length
Liquid
(m)
3/8'' (Ф9.52)
5
10
Min.
Max.
length
Elevation
(m)
B (m)
3
10
Max.
Additional
Length
refrigerant
A (m)
(g/m)
25
40