8.3 Main Protection

8.3.1 Three Minutes Delay at restart for compressor
st
1 minute delay for the 1
time start-up and 3 minutes delay for others.
8.3.2 Temperature protection of compressor top
The unit will stop working when the compressor top temp. protector cut off, and will restart after the
compressor top temp. protector restart.
8.3.3 Temperature protection of compressor discharge
When the compressor discharge temp. is getting higher, the running frequency will be limited as below
rules:
---Compressor discharge temp. T5>115
for 5s, compressor stop
s.
---108<T5<115 , decrease the frequency to the lower level every 3 minutes.
---90<T5<105℃, keep running at the current frequency.
----T5<90 , no limit for frequency.
8.3.4 Fan Speed is out of control
When Indoor Fan Speed keeps too low (300RPM) for certain time, the unit will stop and the LED will
display the failure
8.3.5 Inverter module Protection
The Inverter module has a protection function about current, voltage and temperature. If these
protections happen, the corresponding code will display on indoor unit and the unit will stop working.
8.3.6 Indoor fan delayed open function
When the unit starts up, the louver will be active immediately and the indoor fan will open 10s later.
8.3.7 Compressor preheating functions
Preheating permitting condition:
If T4(outdoor ambient temperature)<3
and the machine connects to power supply newly or if T4
3
and compressor has stopped for over 3 hours, the compressor heating cable will work.
Preheating mode:
A weak current flow through the coil of compressor from the wiring terminal of the compressor, then the
compressor is heated without operation.
Preheating release condition:
If T4>5℃ or the compressor starts running, the preheating function will stop.