Calling Up The Service Level - Viessmann Vitotronic 200 Operating Instructions Manual

Vitodens 200-w, b2ha models 45 to 150 wall-mounted, gas-fired condensing boiler in conjunction with the vitotronic 300-k mw2c cascade control for operation with natural gas and liquid propane gas heating input 55 to 530 mbh 16 to 150 kw read and s
Table of Contents

Advertisement

Further Adjustments

Calling up the Service Level

Press OK and
simultaneously for approximately 4
seconds.
Service menu overview
Service
Exiting the service level
1. Select "Terminate service?".
2. Select "Yes".
3. Confirm with OK.
Note: The service level is automatically exited after
30 minutes.
Scanning operating data
- Operating data can be scanned in six areas.
See "Diagnosis" in the service menu overview.
Operating data on heating circuits with mixing valves
and solar can only be scanned if the components are
installed in the system. For further information on
operating data, see chapter "Brief scan".
Note: "- - -" appears on the display if a sensor that has
been scanned is faulty.
12
Diagnosis
Actuator test
Coding level 1
Coding level 2
Fault history
Service functions
Terminate service?
Note: Do not adjust menu item "Multi-boiler system".
The menu item turns a constant temperature
control unit into a weather-compensated control
unit.
General
Brief scan
Reset data
Participant check
Service PIN
Enter Vitocom PIN code
Service reset
Filling
Venting
Maximum output
Multi-boiler system
Calling up operating data
1. Press OK and
simultaneously for approximately
4 seconds.
2. "Diagnosis"
3. Select required group, e.g. "General
Resetting operating data
Saved operating data (e.g. hours run) can be reset to 0.
The value "Adjusted outside temp" is reset to the actual
value.
1. Press OK and
simultaneously for approximately
4 seconds.
2. "Diagnosis"
3. "Reset data"
4. Select required value (e.g. "Burner starts") or
"All details".