Connecting the earth bonding
Connect the earth bonding in
accordance with the requirements
stipulated by your local electricity
supply company and current local
regulations.
Connecting the heating water side
Note
H Adjust the control thermostat and high limit safety cut-out to ensure that
the DHW temperature inside the DHW cylinder never exceeds 95 ºC.
H Connect the pipework with detachable fittings.
Permiss. heating water flow temp.
Permiss. operating pressure
H heating water side
H DHW side
Test pressure
H heating water side
H DHW side
Permiss. DHW temperature
8
Individual
Cylinder bank with
cylinder
Viessmann header
200 ºC
120 ºC
25 bar
18 bar
10 bar
10 bar
40 bar
13 bar
95 ºC
160 ºC
180 ºC
16 bar
15 bar
10 bar
10 bar