Summary of Contents for Viessmann Vitoflame 300 VHG III
Page 1
VIESMANN Service instructions for contractors Vitoflame 300 Type VHG III Pressure-jet oil burner for the Vitorondens 200-T, 67.6 to 107.3 kW For applicability, see the last page VITOFLAME 300 Please keep safe. 5831447 GB 6/2016...
Page 2
Prior to commencing any work, touch earthed lidate our warranty. objects such as heating or water pipes to dis- For replacements, use only original spare parts charge static loads. supplied or approved by Viessmann.
Page 3
Safety instructions Safety instructions (cont.) Safety instructions for operating the system If you smell flue gas Danger Leaking or blocked flue systems, or an inade- Danger quate supply of combustion air can cause life Flue gas can lead to life threatening poisoning. threatening poisoning from carbon monoxide in ■...
Commissioning, inspection, maintenance Commissioning the system To obtain optimum combustion values, the burner must be adjusted with the boiler heated up (min. 60 C). Also ° carry out tests at base load. Boiler control unit service instructions Note For fuel details, see chapter "Information on fuel oil". 1.
Page 7
Commissioning, inspection, maintenance Checking the oil pressure and vacuum , adjusting… (cont.) 01. Switch system OFF at mains isolator and safe- guard against unauthorised reconnection. 02. Unscrew plug "P" from the oil pump. 03. Unscrew plug "V" from the oil pump. Note Oil may leak from the oil pump when doing this.
Commissioning, inspection, maintenance Checking the oil pressure and vacuum , adjusting… (cont.) 08. Test to check the actual emission values after adjusting the oil pressure. 09. Switch system OFF at mains isolator and safe- guard against unauthorised reconnection. 10. Undo the pressure and vacuum gauges. 11.
Commissioning, inspection, maintenance Cleaning and testing the flame monitor Safety check Response Burner start with dark- Fault shutdown at the end ened flame monitor of the safety time. Red flashing code, flashes Burner start with exter- Fault shutdown after max. nally lit flame monitor 40 s.
Commissioning, inspection, maintenance Cleaning the burner For cleaning the combustion chamber and flues, see boiler service instructions. Fig. 8 1. Set the burner into its maintenance position. To do 3. In the case of severely deviating burner pressure: this, remove nozzle cover with mixing device Remove burner cover and clean casing with...
Commissioning, inspection, maintenance Replacing the nozzle 1. Remove the nozzle cover with mixer device and slot it onto the burner casing with the blast tube connection pointing upwards (service position). This prevents the formation of bubbles in the blast tube connection. 2.
Commissioning, inspection, maintenance Checking and adjusting the ignition electrodes Fig. 10 1. Check ignition electrodes for wear, contamina- Rated heating out- Dim. a Dim. b tion and size accuracy (see diagram), replace if required. 63/67.6 kW 9.4 mm 80/85.8 kW 5 mm 10.0 mm 2.
Commissioning, inspection, maintenance Checking the oil lines and connections for leaks Re-testing the burner and entering the actual values into the report Operating and service documents 1. Complete and detach the customer registration 2. File all parts lists, operating and service instruc- card: tions in the folder and hand this over to the system ■...
Burner control unit Burner control unit Program sequence during commissioning TR/STB 2. Stage 2 BV2 control cam 1. Stage 1 Start required input signals control signals Fig. 13 Note Controlled shutdown The output signal at the solenoid valve stage 2 Burner motor dependent upon the switch position of the BV2 control Solenoid valve stage 2...
Page 16
Burner control unit Burner control unit (cont.) 1. Hold down reset button for approx. 5 s ( 3 s). > 2. A flash code is then shown. The number of flashes in a sequence indicates the type of fault. For an explanation, see the table in chapter "Faults with flash code indication".
Page 17
Burner control unit Burner control unit (cont.) Reset burner control unit: Press reset button for approx. 1 s (<3 s) Burner start...
Troubleshooting Diagnosis Faults with flash code indication Fault Red flash Cause of fault Action code Burner does not start (with 10 x Wiring fault or internal burner Check the electrical connection fault indication), indicator il- fault; not all consumers were rec- luminates ognised;...
Troubleshooting Diagnosis (cont.) Fault Red flash Cause of fault Action code Burner starts and flame Flame monitor contaminated Clean flame monitor × builds, but burner enters Flame monitor receives insuffi- Clean sensor plate × fault state after safety time cient light expires Flame monitor faulty Replace flame monitor...
Page 20
Troubleshooting Diagnosis (cont.) Fault Cause of fault Action Excessive flue gas temper- Excessive oil throughput Match oil throughput to rated boiler heat- ature ing output Boiler contaminated Clean boiler and correct burner settings Air in flue gas heat exchanger Vent flue gas heat exchanger Flue gas heat exchanger contaminated Clean flue gas heat exchanger Not all consumers are connected to the...
Component overview Component overview Fig. 15 Service switch (for burner adjustment) Suction line or return line (differs subject to manu- Hood adaptor facturer) Quick-action fastener Solenoid valve, stage 2 Electronic ignition unit Solenoid valve, stage 1 Servomotor Flame monitor Burner control unit Return line or suction line (differs subject to manu- facturer)
Page 22
Component overview Component overview (cont.) Fig. 16 Reset button Blast tube connection Oil line Flame tube Oil pump Mixing device Fan motor Oil burner nozzle Fan casing Ignition electrodes Impeller Ignition cable Inlet air silencer Flange Air regulating valve Adaptor pipe...
Connection and wiring diagram Connection and wiring diagram Fig. 17 Burner control unit (see chapter "Program Colour coding to DIN IEC 60757 sequence during commissioning") Black Fault indicator Black wire with imprint Reset button Brown Burner motor Blue Service switch (burner stage 2) Flame monitor GN/YE Green/yellow...
Parts lists Parts lists Ordering parts The following information is required: Standard parts are available from your local supplier. ■ Serial no. (see type plate ■ Assembly (from this parts list) ■ Position number of the individual part within the assembly (from this parts list) Overview of assemblies Fig.
Report Report Settings and test values Commissioning Maintenance/service (Set values, see chapter "Standard values for burner adjustment", page ) Oil pressure Stage 1 actual ■ Stage 2 actual ■ Vacuum actual after maintenance bar Soot value Stage 1 actual ■ after maintenance Stage 2 actual...
Standard values for burner adjustment Standard values for burner adjustment Rated heating output of the boiler = 50/30 67.6 85.8 107.3 ° = 80/60 ° Oil burner nozzle Make: Danfoss Type ° ° ° 1.35 1.75 Oil pressure approx. Stage 1 bar min.
The use of combustion improvers that leave res- idues is not permissible. Biofuels Biofuels are made from vegetable oil, e.g. sunflower or rapeseed oil. Please note Biofuels can lead to damage to Viessmann oil burners. Their use is not permissible.
Keyword index Keyword index Flash code..............18 Additives for fuel oil............ 34 Flowchart, burner faults..........16 Air damper position............8 Fuel oil Air damper servomotor, checking the settings..... 8 – Additives..............34 – Quality..............34 Biofuels..............34 Burner cleaning............10 Ignition air setting............8 Burner control unit Ignition electrodes, checking and adjusting....
Need help?
Do you have a question about the Vitoflame 300 VHG III and is the answer not in the manual?
Questions and answers