3.3.6 Configure Strobe Submenu

The configuration parameters for the strobe are the same as those for relays. A strobe would not normally
require a minimum on time but this parameter allows a more versatile configuration.
3.3.6.1 Strobe Summary
This display example shows that the strobe has been configured to operate Normally Off, with a turn on delay
and no minimum on time.
Notice that the strobe number, 5, is underlined. This indicates that the digit keys can be used to jump to a
particular relay, horn or strobe. The relays are numbers 1, 2 and 3; the horn is number 4 and the strobe is 5.
3.3.6.2 Strobe Mode
This display example shows that the strobe is configured to operate in the Normally Off mode. The valid modes
are:
3.3.6.3 Strobe Turn On Delay
The default turn on delay is one minute and the maximum allowed value is fifteen minutes.
3.3.6.4 Strobe Minimum On Time
The default minimum on time is zero and the maximum allowed value is fifteen minutes.
Revision 0.07
S t r o b e 5
D e l a y

Figure 3-37 Strobe Summary

S t r o b e
M o d e : 2

Figure 3-38 Strobe Mode

2
Normally Off (default)
3
Normally On
S t r o b e
( m m : s s )

Figure 3-39 Strobe Turn On Delay

S t r o b e
( m m : s s )

Figure 3-40 Strobe Minimum on time

N o r m . O f f
O n
N o r m . O f f
D e l a y
0 1 : 0 0
M i n . O n
0 0 : 0 0
O n