3.3.2.2 Set Day of Week
This display example shows that Tuesday is the current day of the week. The underline character indicates that
the day can be changed by entering the corresponding digit:
3.3.2.3 Load Default Configuration
When the one (1) digit is pressed, the panel will prompt for the password, even if it has been entered previously.
If the password is entered correctly, the panel will overwrite the existing configuration with the default
configuration. This operation is intended to restore the panel to a known basic condition if it is removed from
one installation and installed in another.
The default configuration is:
Password
Sensors
Alarm levels
Alarm signals
Warning signals
Trouble signals
Warning Levels
Sensor Range
Relay 1
Relay 2
Relay 3
Horn
Strobe
Zone1
Zone2
Zone3
Rising Trip Levels CO = 100 ppm, HS = 2.5ppm, EX = 2,000 ppm
Falling Trip Levels CO = 50 ppm, HS = 1.2 ppm, EX = 1,000 ppm
Revision 0.07
T i m e :
D a y : 2

Figure 3-19 Set Day of the week

1
Monday
2
Tuesday
3
Wednesday
4
Thursday
5
Friday
6
Saturday
7
Sunday
1
L o a d
C o n f i g u r a t i o n

Figure 3-20 Load Default Configuration

1234
Undefined
CO = 200 ppm, HS = 5.0ppm, EX = 4,000 ppm
Buzzer = Intermittent, Horn = Intermittent, Strobe = Continuous
Buzzer = Double Tap, Horn = Off, Strobe = Off
Buzzer = Triple Tap, Horn = Off, Strobe = Off
CO = 200 ppm, HS = 5.0 ppm, EX = 4,000 ppm
CO = 200ppm, HS = 6.0 ppm, EX = 10,000 ppm
Normally off, 1 minute turn on delay, 1 minute minimum on time
Normally off, 1 minute turn on delay, 1 minute minimum on time
Normally off, 1 minute turn on delay, 1 minute minimum on time
Normally off, 1 minute turn on delay, 0 (zero) minimum on time
Normally off, 1 minute turn on delay, 0 (zero) minimum on time
Controls nothing, no sensors assigned, Voting mode, Quorum = 1
Controls nothing, no sensors assigned, Voting mode, Quorum = 1
Controls nothing, no sensors assigned, Voting mode, Quorum = 1
2 2 : 5 5
T u e s d a y
D e f a u l t
22