3.3.5 Configure Horn Submenu

The configuration parameters for the horn are the same as those for relays. A horn would not normally require a
minimum on time but this parameter allows a more versatile configuration.
3.3.5.1 Horn Summary
This display example shows that the horn has been configured to operate Normally Off, with a turn on delay
and no minimum on time.
Notice that the horn number, 4, is underlined. This indicates that the digit keys can be used to jump to a
particular relay, horn or strobe. The relays are numbers 1, 2 and 3; the horn is number 4 and the strobe is 5.
3.3.5.2 Horn Mode
This display example shows that the horn is configured to operate in the Normally Off mode. The valid modes
are:
3.3.5.3 Horn Turn On Delay
The default turn on delay is one minute and the maximum allowed value is fifteen minutes.
3.3.5.4 Horn Minimum On Time
The default minimum on time is zero and the maximum allowed value is fifteen minutes.
Revision 0.07
H o r n
4
D e l a y

Figure 3-33 Horn Summary

H o r n
M o d e : 2

Figure 3-34 Horn Mode

2
Normally Off (default)
3
Normally On
H o r n
( m m : s s )

Figure 3-35 Horn Turn On Delay

H o r n
( m m : s s )

Figure 3-36 Horn Minimum on time

N o r m . O f f
O n
N o r m . O f f
D e l a y
0 1 : 0 0
M i n . O n
0 0 : 0 0
O n
27