I Oil recovery in the heating
1. This is an operation mode to recover compressor oil that moved to pipe or indoor unit after mixing with refrigerant during opera-
tion.
2. Use the K1 Key
3. Automatic operation by the basic setting time during heating operation
4. Use the key mode if required
The number of pressing
7 times : MAIN

10-3-3 Vacuum Preparing Operation

I Make the condition of the outdoor unit vacuum preparing operation
1. Purpose :
According to the valves such as EEV, Solenoid Valve, and Check Valve, the vacuum and the emission of refrigerant may not be
succeeded smoothly. Therefore, insert a separate operation mode for the vacuum or the complete emission of refrigerant.
2. Use the K1 key
3. Determine an operation outdoor unit
The number of pressing
8 times: Main unit
9 times: Sub1 unit
10 times: Sub2 unit
11 times: Sub3 unit
12 times: All unit
4. Operation Method :
All the EEV of the outdoor unit on the vacuum mode is opened to the maximum degree of openness and all the Solenoid Valve is
waited on the open state.