Outdoor Unit Fan Motor Rpm Error - Samsung AVXC1H022 series Service Manual

System air conditioner
Table of Contents

Advertisement

I Outdoor Unit Fan Motor High Temperature Error
Outdoor unit display
Indoor unit display
Judgment method
Causes
1. Check Method
1) The system is programmed that operating after cooling the motor by lowering the number of rotation of the motor in
case of the overload and error action as for the motor protecting action. If the motor is operated, there is no error.
2) Check whether there is rotation of the outdoor Fan Motor and whether there is a lock.
3) Possible to operate after removing the cause of the lock in case of the lock.
I Outdoor Unit Fan Motor RPM Error
Outdoor unit display
Indoor unit display
Judgment method
Causes
1. Check Method
1) The system is programmed that operating by attempting to restart several times to operate the motor if an error signal
is generated on the starting defect. If the motor is operated, there is no error.
2) Check whether the outdoor unit Fan Motor is rotated and locked or not.
3) Check the motor and the signal terminal connection status.
4) If the motor is not operated, the motor defect is judged.
Samsung Electronics
-
When the temperature of the outdoor Fan Motor operated is overheated at over 110°C
Indoor unit Fan Motor lock or defect
-
When the difference between the number of rotation of the outdoor Fan Motor under an
operation and an ordered value is over 100rpm
Indoor unit Fan Motor lock or defect
Troubleshooting
9-28