Samsung AVXC1H022 series Service Manual page 306

System air conditioner
Table of Contents

Advertisement

I
: Digital Compressor Discharge Temperature Sensor Error (Open/Short)
Outdoor unit display
Indoor unit display
Judgment method
Causes
Is separated the outdoor
Discharge temperature sensor
connector from PCB?
Detach the outdoor discharge temperature
sensor connector from PCB and measure the
resistance value between the both terminals.
Is the resistance value
temperature table?
Restart after replacing PCB.
Samsung Electronics
(Operation)
Refer to the below judgment method
Digital compressor discharge temperature sensor open/short defect
Yes
Yes
far from the
Yes
(Timer)
(Fan)
(Filter)
No
Restart after connecting a
connector to PCB.
No
Replace the outdoor heat exchanger
temperature sensor because it is defect.
Temperature
Resistance
(°C)
(KΩ)
130
120
100
18.5
80
60
25
20
10
0
-10
MUF-0601
(Defrost)
Temperature
(°C)
8.9
130
11.2
120
100
32
80
59
60
200
25
242
20
362
10
553
0
-10
Another model
(model used PWM compressor)
Troubleshooting
Resistance
(KΩ)
2.6
3.4
5.8
10.8
21
86
107
171
280
475
9-62

Hide quick links: