10-2-3 Test operation

Precautions before the test operation
• Preheat the crankcase heater by turning the switch on before 6 hours to test operation.
• If the heater is not heated right after switch ON, it dose not operate during 2 hours 30 minutes to protect a
compressor. (On this occasion, CH is displayed on the check display part of outdoor unit PCB.)
I Pre-check for the test operation
1. Check the indoor and outdoor unit power
cable, and communication wire.
G Electric part F1-Indoor unit F1/ Electric instrument F2-Indoor
unit F2
2. Preheat the compressor crankcase heater by
turning power breaker(3 phases & single
phase) on before 6 hours to test operation.
G Power ON 3 phases first, and single phase.
G If the crankcase heater is not heated, CH is displayed on
the check display part of outdoor unit.
G On CH status, the outdoor dose not operate. Be sure to not
break the compressor by a forced operation.
G The crankcase heater uses single phase power(220V).
3. Check the power between the outdoor unit and
the cabinet panel.
G Check the power L1(RED), L2(WHITE), and L3(BLACK)
3 phases of the compressor and the cabinet panel by use of
3 phases tester.
G Check the 220V by use of the tester.
Samsung Electronics
Indoor unit 0
Indoor unit 1
Outdoor
unit
Single phase
3 phases
Reference Information
Electronic
component
box
PCB check win-
dow
3 phases power
detection
C
o
m
p.
Crankcase
heater
3 phases tester
10-6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents