12
6. Operation with 1 compressor
7. With B0 / W35 according to EN255: Heat output 66.4 kW; coefficient of performance 3.6
8. Considerably higher coefficients of performance are achieved by means of cooling operation and waste heat recovery via additional heat exchangers.
9. The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation with a flow temperature of 35°C. The specified sound pressure level
represents the free sound area level. The measured value can deviate by up to 16 dB(A), depending on the installation location.
10.Necessary for ensuring waste heat recovery in cooling operation.
11.Note that additional space is required for pipe connections, operation and maintenance.
12.See CE declaration of conformity
13.The heat circulating pump and the heat pump manager must always be ready for operation.