Start-up

Start-up Information

Initial start-up

Initial start-up must be performed by qualified personnel;
values and calibrations specified in the Technical Data
section on page 38 in this manual are to be recorded
at this time.

Instructing the system user

The installer of the system is responsible to ensure the
system operator/ultimate owner is made familiar with
the functioning of the system, its activation, and its
shut-down. The following topics must be covered:
H Proper system operation sequence.
H Explain the equipment as well as the need for
combustion air.
H Demonstrate an emergency shut-down,
what to do and what not.
H Explain that there is no substitute for proper
maintenance to help ensure safe operation.
H Annual inspection is recommended.

Shut-down

Deactivate main power to heating boiler(s) and burner(s)
if burners have separate power supply, and deactivate
power to circulating pump(s). Close all boiler isolation
valve(s) as well as all fuel supply valve(s).

Extended shut-down periods

If after the heating period the boiler is shut down for
the summer months (no domestic hot water production),
the boiler should be properly cleaned, incl. combustion
chamber, flue gas passageways, and, as necessary,
vent pipe connector, to avoid corrosion.
The boiler and system must remain filled with water.
Do not drain boiler or heating system.
36
Vitorond 200, VD2A Series Installation

Start-up after extended shut-down

If the system was shut down for an extended period
of time, restart and recondition the system.
H Ensure all national and/or local rules and regulations
have been adhered to in this installation. Do not
attempt to start the boiler if you smell gas. If you smell
gas, open windows. Do not touch electrical switches,
extinguish any open flame, close all gas valves
immediately. Call your gas supplier immediately from
a neighbor's phone.
H For oil burners, do not reset the burner flame safeguard
control more than two times.
H Check system for proper water fill (cold fill pressure).
Ensure that complete system is properly vented.
Adjust automatic feed valve to proper desired fill
pressure. Do not tamper with the unit or controls.
Never burn garbage or paper in the unit or leave
combustible materials around it.
WARNING
If system is subject to freezing temperatures and
is not filled with antifreeze for protection, the system
including the boiler must be drained of water.
The valve before the automatic feed valve (if installed)
must be closed; any other valves, air vents and drain
valves must stay open.
Depending on the control system utilized, reprogramming
of the control system might be necessary in the event
of lengthy power interruption.