Venting (Option #2); Flue Gas Connection - Viessmann VITOROND 200 VD2A-125 Installation Instructions Manual

Vd2a series oil-/gas-fired boiler
Hide thumbs Also See for VITOROND 200 VD2A-125:
Table of Contents

Advertisement

Vitorond 200, VD2A Series Installation
Venting Connections

Venting (option #2)

The Vitorond 200 boiler is a Category III positive pressure
non-condensing boiler.
Each boiler must be vented individually.
The vent system must be properly designed and suitable
materials must be selected. The chimney must be gas
tight.
Use an AL29-4C® special stainless steel venting system
(UL/ULC listed for Category III) for single-wall vertical
venting of the Vitorond 200 boiler.
For more details on the positive pressure venting option,
see the Viessmann installation instructions for the positive
pressure venting system.
IMPORTANT
The flue size outlet of the boiler does not automatically
determine the horizontal breeching, or the actual chimney
diameter. The chimney size must be designed for the
actual boiler model and its respective input.
Please refer to the Positive Pressure Venting
System Installation Instructions.

Flue Gas Connection

(continued)
The following manufacturers may be contacted for
suitable stainless steel chimneys:
ProTech Systems Inc.
26 Gansevoort Street
Albany, NY 12202
Tel.: (518) 463-7284
Fax: (518) 463-5271
Toll free: 1-800-766-3473
Selkirk Canada Corporation
375 Green Road
Stoney Creek, ON L8E 4A5
Tel.: (905) 662-6600
Fax: (905) 662-5352
(US) 1-800-992-8368
(Canada) 1-888-735-5475
Email: info@selkirkcorp.com
Web: www.selkirkchimney.com
Security Chimneys International Ltd.
2125 Rue Monterey, Laval, Quebec H7L 3T6
Tel. 450-973-9999
(US) 1-800-361-4909
(Canada) 1-800-667-3387
Fax: 450-973-2222
Email: infoeng@securitychimneys.com
Web: www.securitychimneys.com
1. Connect the flue outlet with the shortest possible
run and with a slight upward slope to the chimney
stack. Avoid sharp bends in the flue path. Flue outlet
outside Ø 8 in. (200 mm)
2. Create a flue gas test point by drilling a e in. (10 mm)
hole on the side of the vent pipe approximately two
to three times the vent pipe diameter away from the
flue gas collar of the boiler.
3. Seal and insulate the vent pipe.