Burner Calibration; Weishaupt Burners / Riello Burners; Flue Gas Resistance; Burner Manufacturer - Viessmann VITOROND 200 VD2A-125 Installation Instructions Manual

Vd2a series oil-/gas-fired boiler
Hide thumbs Also See for VITOROND 200 VD2A-125:
Table of Contents

Advertisement

Vitorond 200, VD2A Series Installation
Burner Installation
(continued)

Burner calibration

Weishaupt burners / Riello burners

A Vitorond 200, VD2A boiler with a high-performance
gas burner installed can achieve a combustion efficiency
of up to 85.2%, and up to 87.9% if equipped with a #2
oil burner as follows:
Gas-fired
10% volume CO
, 280°F (138°C) net stack temperature,
2
CO in ppm < 50
Oil-fired
13% volume CO
, 300°F (149°C) net stack temperature,
2
smoke spot 0 - 1 (on the Bacharach Scale)
See separate instructions supplied with the burner.
The maximum input published for each boiler size must
not be exceeded.
Model
VD2A-125
VD2A-160
VD2A-195
VD2A-230
VD2A-270

Burner manufacturer

Weishaupt or Riello

Burner/Gas train approval

Standard approvals are CSA (for Canada) and UL (for
U.S.). IRI and FM approved equipment is also available -
please inquire.

Electrical requirements

Weishaupt W Series and Riello burners are available
in 120 VAC, single-phase, in a 60 Hz configuration.
It is generally acceptable to use voltages within ten
percent of the supply voltage. Available voltage inside
boiler room must be provided at time of order. Ensure
appropriate disconnect means and overcurrent protection.

Natural gas pressure

Natural gas pressures and heating values as provided
by the gas utilities vary greatly across North America.
Select the appropriate gas train accordingly.
Low pressure gas trains have a maximum input of 14 "w.c.;
high pressure gas trains have a maximum pressure of
5 psig. Minimum gas pressures apply - please inquire.
Gas pressures and heating values at site must be
provided at time of order.
Burner

Flue gas resistance

mbar
"w.c.
0.65
0.26
0.95
0.38
1.0
0.40
1.2
0.48
1.6
0.64
33