Vitorond 200, VD2A Series Installation

Assembly of Boiler Base

Legend
a with adjustable feet (standard delivery)
 1.26 in. (32 mm)
a with adjustable anti-vibration feet (optional)
1.73 in. (44 mm)
1 Boiler base length
Boiler model 125 - 24 in. (600 mm)
Boiler model 160 - 30 in. (770 mm)
Boiler model 195 - 37 in. (940 mm)
Boiler model 230 - 44 in. (1110 mm)
Boiler model 270 - 50 in. (1280 mm)
1. Install levelling bolts and adjust to lowest setting.
2. Level the boiler base with the levelling bolts.
*1
Anti-vibration feet available (optional).
IMPORTANT
For recommended service clearance from the boiler to the
wall C, see page 11.
1. Screw in bolts or anti-vibration bolts (levelling foot B
only for boiler sizes 230 and 270).
2. Install crossbar A with its larger cut-out pointing
to the front of the boiler.