constructed to prevent rain, snow, leaves and other foreign
bodies from entering the chimney,
constructed to enable expulsion of combustion products in
case of wind from any direction and incline,
installed
combustion products outside the reflux zone (backflow)
because the counter pressure occurs here. Therefore, it is
necessary to adhere to limitations listed in figure 15,
mechanical appliances for flue gases suction are not allowed.
FLAT ROOF
table 4
Distance between the
Roof
roof ridge and the
slope
15°
30°
45°
60°
SENKO pellet AIR stoves – Instruction manual
to
enable
proper
Figure 15
chimney
A, m
< 1,85
> 1,85
< 1,5
> 1,5
< 1,3
> 1,3
< 1,2
> 1,2
dispersion
and
PITCHED ROOF
Minimum chimney height
(measured from the roof
surface)
H
, m
min
0,5 m above the roof ridge
1 m from the roof
0,5 m above the roof ridge
1,3 m from the roof
0,5 m above the roof ridge
2 m from the roof
0,5 m above the roof ridge
2,6 m from the roof
dilution
of
Z=REFLUX ZONE