Gas Connections Connecting Gas Supply Piping - Lochinvar Shield SNR200-100 Installation And Service Manual

Lochinvar commercial water heater installation & service manual
Hide thumbs Also See for Shield SNR200-100:
Table of Contents

Advertisement

7
Gas connections
Connecting gas supply piping
1. Install ground joint union for servicing, when
required.
2. On Models SNR150-100 -- SNA285-125 install a manual
shutoff valve in the gas supply piping outside water heater
jacket when required by local codes or utility
requirements.
3. In Canada – When using manual main shutoff
valves, it must be identified by the installer.
Figure 7-1 Gas Supply Piping - Models SNR150-100 --
SNA285-125
GAS SUPPLY
DRIP LEG
Figure 7-2 Gas Supply Piping - Models SNA400-125 --
SNA500-125
MANUAL GAS
SHUTOFF VALVE
(FACTORY SUPPLIED ON
MODELS SNA400-125 --
SNA500-125)
GAS SUPPLY
DRIP LEG
4. Support piping with hangers, not by the water heater or its
accessories.
WARNING
5. Purge all air from the gas supply piping.
6. Before placing the water heater in operation, check the
water heater and its gas connection for leaks.
a.
b.
UNION
MANUAL GAS
SHUT OFF VALVE
c.
(FIELD SUPPLIED)
WARNING
7. Use pipe sealing compound compatible with propane gases.
Apply sparingly only to male threads of the pipe joints so
that pipe dope does not block gas flow.
UNION
Installation & Service Manual
TM
The gas valve and blower will not support
the weight of the piping. Do not attempt to
support the weight of the piping with the
water heater or its accessories. Failure to
comply could result in severe personal
injury, death, or substantial property
damage.
The appliance must be disconnected from the gas
supply piping system during any pressure testing of
that system at a test pressure in excess of 1/2 PSIG
(3.5 kPa).
The appliance must be isolated from the gas supply
piping system by closing a manual shutoff valve
during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 PSIG
(3.5 kPa).
The appliance and its gas connection must be leak
tested before placing it in operation.
Do not check for gas leaks with an open
flame – use the bubble test. Failure to use
the bubble test or check for gas leaks can
cause severe personal injury, death, or
substantial property damage.